All MIBs › LIEBERT-GP-POWER-MIB › lgpPwrBatteryEndOfDischargeVoltage
lgpPwrBatteryEndOfDischargeVoltage
Module: LIEBERT-GP-POWER-MIB
OID (symbolic): LIEBERT-GP-POWER-MIB::lgpPwrBatteryEndOfDischargeVoltage
OID (numeric): 1.3.6.1.4.1.476.1.42.3.5.1.11
Node type: OBJECT-TYPE
Type: Integer32
Access: read-write
Description: The battery voltage threshold at which the batteries are considered completely discharged.
What is lgpPwrBatteryEndOfDischargeVoltage?
The voltage threshold below which the batteries are considered fully discharged. The UPS uses this setpoint to decide when to trigger a low-battery shutdown before the battery is damaged by over-discharging.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.1.11 snmpwalk -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrBatteryEndOfDischargeVoltage
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.1.11.1 snmpget -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrBatteryEndOfDischargeVoltage.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.42.3.5.1.11.1 i <value>
Start monitoring Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-POWER-MIB::lgpPwrBatteryEndOfDischargeVoltage OID value, configure state conditions and alerts, and monitor any Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42 | liebertGlobalProducts | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3 | lgpFoundation | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3.5 | lgpPower | LIEBERT-GP-REGISTRATION-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.42.3.5.1 | lgpPwrBattery | LIEBERT-GP-POWER-MIB |
| 1.3.6.1.4.1.476.1.42.3.5.1.11 | lgpPwrBatteryEndOfDischargeVoltage | LIEBERT-GP-POWER-MIB |