All MIBs › LIEBERT-GP-PDU-MIB › lgpPduRcpEntryPwrOnDelay
lgpPduRcpEntryPwrOnDelay
Module: LIEBERT-GP-PDU-MIB
OID (symbolic): LIEBERT-GP-PDU-MIB::lgpPduRcpEntryPwrOnDelay
OID (numeric): 1.3.6.1.4.1.476.1.42.3.8.50.20.1.90
Node type: OBJECT-TYPE
Type: Unsigned32
Access: read-write
Description: The amount of time to wait before power is applied to the receptacle after a power strip is turned on or rebooted. This can be used to stagger the powering of multiple receptacles in order to prevent a large initial current draw.
What is lgpPduRcpEntryPwrOnDelay?
A read-write delay, in seconds, before power is applied to this receptacle after the strip is turned on or rebooted, letting admins stagger startup of multiple outlets to avoid a large inrush current when many devices power up together.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.90 snmpwalk -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduRcpEntryPwrOnDelay
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.90.1 snmpget -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduRcpEntryPwrOnDelay.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.90.1 i <value>
Start monitoring Liebert/Emerson power distribution units with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-PDU-MIB::lgpPduRcpEntryPwrOnDelay OID value, configure state conditions and alerts, and monitor any Liebert/Emerson power distribution units from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42 | liebertGlobalProducts | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3 | lgpFoundation | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3.8 | lgpPdu | LIEBERT-GP-REGISTRATION-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.42.3.8.50 | lgpPduReceptacle | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.50.20 | lgpPduRcpTable | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1 | lgpPduRcpEntry | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.90 | lgpPduRcpEntryPwrOnDelay | LIEBERT-GP-PDU-MIB |