LIEBERT-GP-PDU-MIB :: lgpPduRcpEntryLineSource

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › LIEBERT-GP-PDU-MIB › lgpPduRcpEntryLineSource

lgpPduRcpEntryLineSource

Module: LIEBERT-GP-PDU-MIB

OID (symbolic): LIEBERT-GP-PDU-MIB::lgpPduRcpEntryLineSource

OID (numeric): 1.3.6.1.4.1.476.1.42.3.8.50.20.1.45

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-only

Description: This represents the line source that is supplying power to this receptacle. not-specified The line source supplying power to the load for this receptacle has not been specified/configured. line-1-N The load for this receptacle is supplied by a line-to-neutral configuration. (line 1 to neutral). line-2-N The load for this receptacle is supplied by a line-to-neutral configuration. (line 2 to neutral). line-3-N The load for this receptacle is supplied by a line-to-neutral configuration. (line 3 to neutral). line-1-line-2 The load for this receptacle is supplied by a line-to-line configuration (line 1 to line 2). line-2-line-3 The load for this receptacle is supplied by a line-to-line configuration (line 2 to line 3). line-3-line-1 The load for this receptacle is supplied by a line-to-line configuration (line 3 to line 1). unknown-line-neutral The load for this receptacle is supplied by a line-to-neutral configuration. The system is unable to determine which lines are supporting the load. unknown-line-line The load for this receptacle is supplied by a line-to-line configuration. The system is unable to determine which lines are supporting the load.

What is lgpPduRcpEntryLineSource?

An enumeration identifying which upstream line(s) feed this specific receptacle, e.g. line-2-N(2) for a line-to-neutral feed off phase 2, used to understand which phase a given outlet's load draws from.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.45
snmpwalk -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduRcpEntryLineSource

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.45.1
snmpget -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduRcpEntryLineSource.1

Start monitoring Liebert/Emerson power distribution units with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-PDU-MIB::lgpPduRcpEntryLineSource OID value, configure state conditions and alerts, and monitor any Liebert/Emerson power distribution units from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.476emersonLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1liebertCorpLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42liebertGlobalProductsLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3lgpFoundationLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3.8lgpPduLIEBERT-GP-REGISTRATION-MIB
Numeric OIDNameModule
1.3.6.1.4.1.476.1.42.3.8.50lgpPduReceptacleLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.50.20lgpPduRcpTableLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.50.20.1lgpPduRcpEntryLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.50.20.1.45lgpPduRcpEntryLineSourceLIEBERT-GP-PDU-MIB