LIEBERT-GP-PDU-MIB :: lgpPduRcpEntryEnergyAccum

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › LIEBERT-GP-PDU-MIB › lgpPduRcpEntryEnergyAccum

lgpPduRcpEntryEnergyAccum

Module: LIEBERT-GP-PDU-MIB

OID (symbolic): LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEnergyAccum

OID (numeric): 1.3.6.1.4.1.476.1.42.3.8.50.20.1.85

Node type: OBJECT-TYPE

Type: Unsigned32

Access: read-write

Description: Total accumulated energy, measured at the module input, since the last energy reset. Writing a value of 0 (zero) to this causes the accumulated energy to be reset. Writing a non-zero value is invalid and shall result in a write error and the total energy value remains unchanged.

If the energy has not been reset and has not wrapped, then this is the total energy since installation.

This value persists across boot events.

What is lgpPduRcpEntryEnergyAccum?

A read-write accumulated-energy counter (tenths of a kWh) at this specific outlet since the last reset; writing 0 resets it, any other write is rejected. Admins use this for per-outlet energy billing/trending of individual plugged-in equipment.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.85
snmpwalk -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEnergyAccum

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.85.1
snmpget -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEnergyAccum.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.85.1 i <value>

Start monitoring Liebert/Emerson power distribution units with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEnergyAccum OID value, configure state conditions and alerts, and monitor any Liebert/Emerson power distribution units from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.476emersonLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1liebertCorpLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42liebertGlobalProductsLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3lgpFoundationLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3.8lgpPduLIEBERT-GP-REGISTRATION-MIB
Numeric OIDNameModule
1.3.6.1.4.1.476.1.42.3.8.50lgpPduReceptacleLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.50.20lgpPduRcpTableLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.50.20.1lgpPduRcpEntryLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.50.20.1.85lgpPduRcpEntryEnergyAccumLIEBERT-GP-PDU-MIB