All MIBs › LIEBERT-GP-PDU-MIB › lgpPduRcpEntryEnergyAccum
lgpPduRcpEntryEnergyAccum
Module: LIEBERT-GP-PDU-MIB
OID (symbolic): LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEnergyAccum
OID (numeric): 1.3.6.1.4.1.476.1.42.3.8.50.20.1.85
Node type: OBJECT-TYPE
Type: Unsigned32
Access: read-write
Description: Total accumulated energy, measured at the module input, since the last energy reset. Writing a value of 0 (zero) to this causes the accumulated energy to be reset. Writing a non-zero value is invalid and shall result in a write error and the total energy value remains unchanged.
If the energy has not been reset and has not wrapped, then this is the total energy since installation.
This value persists across boot events.
What is lgpPduRcpEntryEnergyAccum?
A read-write accumulated-energy counter (tenths of a kWh) at this specific outlet since the last reset; writing 0 resets it, any other write is rejected. Admins use this for per-outlet energy billing/trending of individual plugged-in equipment.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.85 snmpwalk -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEnergyAccum
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.85.1 snmpget -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEnergyAccum.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.85.1 i <value>
Start monitoring Liebert/Emerson power distribution units with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEnergyAccum OID value, configure state conditions and alerts, and monitor any Liebert/Emerson power distribution units from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42 | liebertGlobalProducts | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3 | lgpFoundation | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3.8 | lgpPdu | LIEBERT-GP-REGISTRATION-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.42.3.8.50 | lgpPduReceptacle | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.50.20 | lgpPduRcpTable | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1 | lgpPduRcpEntry | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.85 | lgpPduRcpEntryEnergyAccum | LIEBERT-GP-PDU-MIB |