All MIBs › LIEBERT-GP-PDU-MIB › lgpPduRcpEntryEcThrshldUnderAlarm
lgpPduRcpEntryEcThrshldUnderAlarm
Module: LIEBERT-GP-PDU-MIB
OID (symbolic): LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEcThrshldUnderAlarm
OID (numeric): 1.3.6.1.4.1.476.1.42.3.8.50.20.1.150
Node type: OBJECT-TYPE
Type: Unsigned32
Access: read-write
Description: The threshold at which an under current alarm is activated. If the measured current (lgpPduRbLineEntryEcLL) is equal to or below this percentage of the full scale rated value (lgpPduRbEntryEcRated), an under current alarm is activated
What is lgpPduRcpEntryEcThrshldUnderAlarm?
A read-write percentage threshold (of the branch's rated current, lgpPduRbEntryEcRated) below which this receptacle's own measured current (lgpPduRcpEntryEc) triggers an under-current alarm. Note: the source DESCRIPTION text literally names a different sibling object (lgpPduRbLineEntryEcLL) as the measured value, which is a copy-paste artifact in the vendor MIB - the object's own name and table position make clear it governs this receptacle's current, not that branch-line object.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.150 snmpwalk -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEcThrshldUnderAlarm
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.150.1 snmpget -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEcThrshldUnderAlarm.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.150.1 i <value>
Start monitoring Liebert/Emerson power distribution units with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-PDU-MIB::lgpPduRcpEntryEcThrshldUnderAlarm OID value, configure state conditions and alerts, and monitor any Liebert/Emerson power distribution units from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42 | liebertGlobalProducts | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3 | lgpFoundation | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3.8 | lgpPdu | LIEBERT-GP-REGISTRATION-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.42.3.8.50 | lgpPduReceptacle | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.50.20 | lgpPduRcpTable | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1 | lgpPduRcpEntry | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.150 | lgpPduRcpEntryEcThrshldUnderAlarm | LIEBERT-GP-PDU-MIB |