Type: INTEGER
Access: read-write
Description: This object represents the locked state of the receptacle.
unknown The lock state of the receptacle is not known at this time. locked If the receptacle is 'locked' then its current persisted (configured) state can not be changed. unlocked If the receptacle is 'unlocked', then a user with proper permissions may change the receptacles state.
What is lgpPduRcpEntryControlLock?
A read-write lock on the receptacle's control state: unlocked(1) allows an authorized user to change its power state via lgpPduRcpEntryControl, while locked(2) prevents any change - useful for protecting critical outlets from accidental remote power-off.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.105 snmpwalk -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduRcpEntryControlLock
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.105.1 snmpget -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduRcpEntryControlLock.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.105.1 i <value>
Start monitoring Liebert/Emerson power distribution units with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-PDU-MIB::lgpPduRcpEntryControlLock OID value, configure state conditions and alerts, and monitor any Liebert/Emerson power distribution units from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42 | liebertGlobalProducts | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3 | lgpFoundation | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3.8 | lgpPdu | LIEBERT-GP-REGISTRATION-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.42.3.8.50 | lgpPduReceptacle | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.50.20 | lgpPduRcpTable | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1 | lgpPduRcpEntry | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.105 | lgpPduRcpEntryControlLock | LIEBERT-GP-PDU-MIB |