LIEBERT-GP-PDU-MIB :: lgpPduRcpEntryControl

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › LIEBERT-GP-PDU-MIB › lgpPduRcpEntryControl

lgpPduRcpEntryControl

Module: LIEBERT-GP-PDU-MIB

OID (symbolic): LIEBERT-GP-PDU-MIB::lgpPduRcpEntryControl

OID (numeric): 1.3.6.1.4.1.476.1.42.3.8.50.20.1.100

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: This object represents the current and persistent (configured) power state of the receptacle. The receptacle can also be controlled by writing to this object. off The current and persisted (configured) power state of the receptacle is 'off'. When writing 'off' to this object the receptacle, if ON, will be turned OFF and its persistent (configured) power state will be set to 'off'. on The current and persisted (configured) power state of the receptacle is 'on'. When writing 'on' to this object the receptacle, if 'off', will be turned 'on' and its persistent (configured) power state will be set to 'on'. cycle-power The receptacle is currently in a power-cycle state. The power to the receptacle is being turned off momentarily and will then revert to being 'on'. When writing 'cycle-power' to this OBJECT if the receptacle is 'on' it will be momentarily turned 'off' and then revert to the 'on' state. The receptacle's persistent (configured) power state will be left unchanged ('on').

If the receptacle is OFF writing cycle-power has no affect on the receptacle.

What is lgpPduRcpEntryControl?

A read-write control that both reports and sets the receptacle's persistent power state - writing off(0), on(1), or cycle-power(2) actually switches the outlet (cycle-power turns it off then back on), making this the primary remote power-switching knob for that outlet.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.100
snmpwalk -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduRcpEntryControl

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.100.1
snmpget -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduRcpEntryControl.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.42.3.8.50.20.1.100.1 i <value>

Start monitoring Liebert/Emerson power distribution units with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-PDU-MIB::lgpPduRcpEntryControl OID value, configure state conditions and alerts, and monitor any Liebert/Emerson power distribution units from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.476emersonLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1liebertCorpLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42liebertGlobalProductsLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3lgpFoundationLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3.8lgpPduLIEBERT-GP-REGISTRATION-MIB
Numeric OIDNameModule
1.3.6.1.4.1.476.1.42.3.8.50lgpPduReceptacleLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.50.20lgpPduRcpTableLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.50.20.1lgpPduRcpEntryLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.50.20.1.100lgpPduRcpEntryControlLIEBERT-GP-PDU-MIB