All MIBs › LIEBERT-GP-PDU-MIB › lgpPduPsLineEntryEcThrshldUndrAlarm
lgpPduPsLineEntryEcThrshldUndrAlarm
Module: LIEBERT-GP-PDU-MIB
OID (symbolic): LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcThrshldUndrAlarm
OID (numeric): 1.3.6.1.4.1.476.1.42.3.8.30.40.1.35
Node type: OBJECT-TYPE
Type: Unsigned32
Access: read-write
Description: The threshold at which an under current alarm is activated. If the measured current (lgpPduPsLineEntryEc) is equal to or below this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an under current alarm is activated.
What is lgpPduPsLineEntryEcThrshldUndrAlarm?
A read-write percentage-of-rated-current threshold; if the measured line current (lgpPduPsLineEntryEc) drops to or below this percentage of lgpPduPsEntryEcInputRated, an under-current alarm fires - useful for detecting an unexpectedly unloaded or disconnected circuit.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.30.40.1.35 snmpwalk -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcThrshldUndrAlarm
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.30.40.1.35.1 snmpget -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcThrshldUndrAlarm.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.42.3.8.30.40.1.35.1 i <value>
Start monitoring Liebert/Emerson power distribution units with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcThrshldUndrAlarm OID value, configure state conditions and alerts, and monitor any Liebert/Emerson power distribution units from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42 | liebertGlobalProducts | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3 | lgpFoundation | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3.8 | lgpPdu | LIEBERT-GP-REGISTRATION-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.42.3.8.30 | lgpPduPowerSource | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.30.40 | lgpPduPsLineTable | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1 | lgpPduPsLineEntry | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1.35 | lgpPduPsLineEntryEcThrshldUndrAlarm | LIEBERT-GP-PDU-MIB |