LIEBERT-GP-PDU-MIB :: lgpPduPsLineEntryEcThrshldOvrWarn

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › LIEBERT-GP-PDU-MIB › lgpPduPsLineEntryEcThrshldOvrWarn

lgpPduPsLineEntryEcThrshldOvrWarn

Module: LIEBERT-GP-PDU-MIB

OID (symbolic): LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcThrshldOvrWarn

OID (numeric): 1.3.6.1.4.1.476.1.42.3.8.30.40.1.36

Node type: OBJECT-TYPE

Type: Unsigned32

Access: read-write

Description: The threshold at which an over current warning is activated. If the measured current (lgpPduPsLineEntryEc) is equal to or over this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an over current warning is activated.

What is lgpPduPsLineEntryEcThrshldOvrWarn?

A read-write percentage-of-rated-current threshold that raises an over-current warning once the measured line current reaches or exceeds it, giving admins an early heads-up before the phase is overloaded.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.30.40.1.36
snmpwalk -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcThrshldOvrWarn

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.30.40.1.36.1
snmpget -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcThrshldOvrWarn.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.42.3.8.30.40.1.36.1 i <value>

Start monitoring Liebert/Emerson power distribution units with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcThrshldOvrWarn OID value, configure state conditions and alerts, and monitor any Liebert/Emerson power distribution units from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.476emersonLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1liebertCorpLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42liebertGlobalProductsLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3lgpFoundationLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3.8lgpPduLIEBERT-GP-REGISTRATION-MIB
Numeric OIDNameModule
1.3.6.1.4.1.476.1.42.3.8.30lgpPduPowerSourceLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.30.40lgpPduPsLineTableLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.30.40.1lgpPduPsLineEntryLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.30.40.1.36lgpPduPsLineEntryEcThrshldOvrWarnLIEBERT-GP-PDU-MIB