LIEBERT-GP-PDU-MIB :: lgpPduPsLineEntryEcThrshldOvrAlarm

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › LIEBERT-GP-PDU-MIB › lgpPduPsLineEntryEcThrshldOvrAlarm

lgpPduPsLineEntryEcThrshldOvrAlarm

Module: LIEBERT-GP-PDU-MIB

OID (symbolic): LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcThrshldOvrAlarm

OID (numeric): 1.3.6.1.4.1.476.1.42.3.8.30.40.1.37

Node type: OBJECT-TYPE

Type: Unsigned32

Access: read-write

Description: The threshold at which an over current alarm is activated. If the measured current (lgpPduPsLineEntryEc) is equal to or over this percentage of the full scale rated value (lgpPduPsEntryEcInputRated), an over current alarm is activated.

What is lgpPduPsLineEntryEcThrshldOvrAlarm?

The higher-severity sibling of the over-current warning threshold: a percentage of rated current that, once equaled or exceeded by the measured line current, triggers a full over-current alarm rather than just a warning.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.30.40.1.37
snmpwalk -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcThrshldOvrAlarm

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.30.40.1.37.1
snmpget -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcThrshldOvrAlarm.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.42.3.8.30.40.1.37.1 i <value>

Start monitoring Liebert/Emerson power distribution units with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEcThrshldOvrAlarm OID value, configure state conditions and alerts, and monitor any Liebert/Emerson power distribution units from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.476emersonLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1liebertCorpLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42liebertGlobalProductsLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3lgpFoundationLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3.8lgpPduLIEBERT-GP-REGISTRATION-MIB
Numeric OIDNameModule
1.3.6.1.4.1.476.1.42.3.8.30lgpPduPowerSourceLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.30.40lgpPduPsLineTableLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.30.40.1lgpPduPsLineEntryLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.30.40.1.37lgpPduPsLineEntryEcThrshldOvrAlarmLIEBERT-GP-PDU-MIB