LIEBERT-GP-PDU-MIB :: lgpPduPsLineEntryEc

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › LIEBERT-GP-PDU-MIB › lgpPduPsLineEntryEc

lgpPduPsLineEntryEc

Module: LIEBERT-GP-PDU-MIB

OID (symbolic): LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEc

OID (numeric): 1.3.6.1.4.1.476.1.42.3.8.30.40.1.21

Node type: OBJECT-TYPE

Type: Unsigned32

Access: read-only

Description: Total input line-to-neutral electrical current. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table.

What is lgpPduPsLineEntryEc?

The total input current for this line/phase, in tenths of an amp AC-RMS, identified by lgpPduPsLineEntryLine. Admins compare this against lgpPduPsEntryEcInputRated to see how heavily that phase is loaded.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.30.40.1.21
snmpwalk -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEc

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.30.40.1.21.1
snmpget -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEc.1

Start monitoring Liebert/Emerson power distribution units with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-PDU-MIB::lgpPduPsLineEntryEc OID value, configure state conditions and alerts, and monitor any Liebert/Emerson power distribution units from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.476emersonLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1liebertCorpLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42liebertGlobalProductsLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3lgpFoundationLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3.8lgpPduLIEBERT-GP-REGISTRATION-MIB
Numeric OIDNameModule
1.3.6.1.4.1.476.1.42.3.8.30lgpPduPowerSourceLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.30.40lgpPduPsLineTableLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.30.40.1lgpPduPsLineEntryLIEBERT-GP-PDU-MIB
1.3.6.1.4.1.476.1.42.3.8.30.40.1.21lgpPduPsLineEntryEcLIEBERT-GP-PDU-MIB