All MIBs › LIEBERT-GP-PDU-MIB › lgpPduPsEntryEnergyAccum
lgpPduPsEntryEnergyAccum
Module: LIEBERT-GP-PDU-MIB
OID (symbolic): LIEBERT-GP-PDU-MIB::lgpPduPsEntryEnergyAccum
OID (numeric): 1.3.6.1.4.1.476.1.42.3.8.30.20.1.50
Node type: OBJECT-TYPE
Type: Unsigned32
Access: read-write
Description: Total accumulated energy, measured at the power source input, since the last energy reset. Writing a value of 0 (zero) to this causes the accumulated energy to be reset. Writing a non-zero value is invalid and shall result in a write error and the total energy value remains unchanged.
If the energy has not been reset and has not wrapped, then this is the total energy since installation.
This value persists across boot events.
What is lgpPduPsEntryEnergyAccum?
A read-write accumulated-energy counter (in tenths of a kWh) measured at the power source input since the last reset; writing 0 resets the counter, and writing any other value is rejected. Admins use it for energy-usage billing or trending, resetting it at the start of a measurement period.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.30.20.1.50 snmpwalk -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduPsEntryEnergyAccum
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.8.30.20.1.50.1 snmpget -v2c -c public <target> LIEBERT-GP-PDU-MIB::lgpPduPsEntryEnergyAccum.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.42.3.8.30.20.1.50.1 i <value>
Start monitoring Liebert/Emerson power distribution units with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-PDU-MIB::lgpPduPsEntryEnergyAccum OID value, configure state conditions and alerts, and monitor any Liebert/Emerson power distribution units from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42 | liebertGlobalProducts | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3 | lgpFoundation | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3.8 | lgpPdu | LIEBERT-GP-REGISTRATION-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.42.3.8.30 | lgpPduPowerSource | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.30.20 | lgpPduPsTable | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1 | lgpPduPsEntry | LIEBERT-GP-PDU-MIB |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1.50 | lgpPduPsEntryEnergyAccum | LIEBERT-GP-PDU-MIB |