All MIBs › LIEBERT-GP-ENVIRONMENTAL-MIB › lgpEnvDehumidifyPropBand
lgpEnvDehumidifyPropBand
Module: LIEBERT-GP-ENVIRONMENTAL-MIB
OID (symbolic): LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvDehumidifyPropBand
OID (numeric): 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.17
Node type: OBJECT-TYPE
Type: Integer32
Access: read-write
Description: The proportional region above the setpoint value (lgpEnvHumiditySetPoint) where dehumidifying will be proportionally controlled.
What is lgpEnvDehumidifyPropBand?
The proportional control band, as a percentage of relative humidity, above lgpEnvHumiditySetPoint within which dehumidifying output is proportionally modulated rather than switched fully on. Admins widen this band for smoother, more gradual dehumidification response as humidity rises above setpoint.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.17 snmpwalk -v2c -c public <target> LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvDehumidifyPropBand
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.17.1 snmpget -v2c -c public <target> LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvDehumidifyPropBand.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.17.1 i <value>
Start monitoring Liebert/Vertiv precision cooling unit (CRAC/CRAH) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvDehumidifyPropBand OID value, configure state conditions and alerts, and monitor any Liebert/Vertiv precision cooling unit (CRAC/CRAH) from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42 | liebertGlobalProducts | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3 | lgpFoundation | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3.4 | lgpEnvironmental | LIEBERT-GP-REGISTRATION-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.42.3.4.2 | lgpEnvHumidity | LIEBERT-GP-ENVIRONMENTAL-MIB |
| 1.3.6.1.4.1.476.1.42.3.4.2.2 | lgpEnvHumidityRelative | LIEBERT-GP-ENVIRONMENTAL-MIB |
| 1.3.6.1.4.1.476.1.42.3.4.2.2.3 | lgpEnvHumidityTableRel | LIEBERT-GP-ENVIRONMENTAL-MIB |
| 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1 | lgpEnvHumidityEntryRel | LIEBERT-GP-ENVIRONMENTAL-MIB |
| 1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.17 | lgpEnvDehumidifyPropBand | LIEBERT-GP-ENVIRONMENTAL-MIB |