All MIBs › LIEBERT-GP-ENVIRONMENTAL-MIB › lgpEnvConfigCompressorLockout
lgpEnvConfigCompressorLockout
Module: LIEBERT-GP-ENVIRONMENTAL-MIB
OID (symbolic): LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigCompressorLockout
OID (numeric): 1.3.6.1.4.1.476.1.42.3.4.4.30
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: The system as locked out the compressor(s). If locked-out, the compressor(s) will not operate even if the controller calls for their operation.
What is lgpEnvConfigCompressorLockout?
Setting to lock out (disable) the compressor(s) even if the controller calls for cooling. Admins set this to lockedOut during maintenance or to force reliance on free cooling, and notLockedOut to restore normal compressor operation.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.4.4.30 snmpwalk -v2c -c public <target> LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigCompressorLockout
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.4.4.30.1 snmpget -v2c -c public <target> LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigCompressorLockout.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.42.3.4.4.30.1 i <value>
Start monitoring Liebert/Vertiv precision cooling unit (CRAC/CRAH) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-ENVIRONMENTAL-MIB::lgpEnvConfigCompressorLockout OID value, configure state conditions and alerts, and monitor any Liebert/Vertiv precision cooling unit (CRAC/CRAH) from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42 | liebertGlobalProducts | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3 | lgpFoundation | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3.4 | lgpEnvironmental | LIEBERT-GP-REGISTRATION-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.42.3.4.4 | lgpEnvConfig | LIEBERT-GP-ENVIRONMENTAL-MIB |
| 1.3.6.1.4.1.476.1.42.3.4.4.30 | lgpEnvConfigCompressorLockout | LIEBERT-GP-ENVIRONMENTAL-MIB |