LIEBERT-GP-CONTROLLER-MIB :: lgpCtrlBoardBatteryVoltage

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › LIEBERT-GP-CONTROLLER-MIB › lgpCtrlBoardBatteryVoltage

lgpCtrlBoardBatteryVoltage

Module: LIEBERT-GP-CONTROLLER-MIB

OID (symbolic): LIEBERT-GP-CONTROLLER-MIB::lgpCtrlBoardBatteryVoltage

OID (numeric): 1.3.6.1.4.1.476.1.42.3.6.6

Node type: OBJECT-TYPE

Type: Unsigned32

Access: read-only

Description: The control board battery voltage. Typically this battery is used to provide backup power to memory and other vital circuits.

What is lgpCtrlBoardBatteryVoltage?

This value reports the voltage of the control board's backup battery, scaled in units of .01 volts as noted in the object's UNITS clause. That battery keeps memory and other vital circuits powered through brief outages, so its voltage is a leading indicator of battery health on the controller board. For instance, a raw reading of 305 (3.05 volts) that steadily declines over weeks would point to a battery nearing end of life and due for replacement.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.6.6
snmpwalk -v2c -c public <target> LIEBERT-GP-CONTROLLER-MIB::lgpCtrlBoardBatteryVoltage

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.6.6.1
snmpget -v2c -c public <target> LIEBERT-GP-CONTROLLER-MIB::lgpCtrlBoardBatteryVoltage.1

Start monitoring Liebert/Vertiv precision cooling and power infrastructure controller with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-CONTROLLER-MIB::lgpCtrlBoardBatteryVoltage OID value, configure state conditions and alerts, and monitor any Liebert/Vertiv precision cooling and power infrastructure controller from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.476emersonLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1liebertCorpLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42liebertGlobalProductsLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3lgpFoundationLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3.6lgpControllerLIEBERT-GP-REGISTRATION-MIB
Numeric OIDNameModule
1.3.6.1.4.1.476.1.42.3.6.6lgpCtrlBoardBatteryVoltageLIEBERT-GP-CONTROLLER-MIB