All MIBs › GUDEADS-EPC2X6-MIB › epc2x6PortState
epc2x6PortState
Module: GUDEADS-EPC2X6-MIB
OID (symbolic): GUDEADS-EPC2X6-MIB::epc2x6PortState
OID (numeric): 1.3.6.1.4.1.28507.6.1.2.2.1.3
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: current state a PowerPort
What is epc2x6PortState?
Reports and controls whether this PowerPort's outlet is currently supplying power (on) or not (off). Admins both read it to check a device's power status remotely and write it to remotely power-cycle equipment, such as rebooting a hung server without physically visiting the rack. To recover a frozen device, an admin would SET epc2x6PortState to off(0), wait a few seconds, then set it back to on(1).
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.28507.6.1.2.2.1.3 snmpwalk -v2c -c public <target> GUDEADS-EPC2X6-MIB::epc2x6PortState
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.28507.6.1.2.2.1.3.1 snmpget -v2c -c public <target> GUDEADS-EPC2X6-MIB::epc2x6PortState.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.28507.6.1.2.2.1.3.1 i <value>
Start monitoring Gude EPC2X6 6-outlet IP power distribution unit (with environmental sensor) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the GUDEADS-EPC2X6-MIB::epc2x6PortState OID value, configure state conditions and alerts, and monitor any Gude EPC2X6 6-outlet IP power distribution unit (with environmental sensor) from a single console.
OID Breakdown
Upper-level ancestors (7 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.28507 | gudeads | GUDEADS-EPC24X-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.28507.6 | gadsEPC2x6 | GUDEADS-EPC2X6-MIB |
| 1.3.6.1.4.1.28507.6.1 | epc2x6Objects | GUDEADS-EPC2X6-MIB |
| 1.3.6.1.4.1.28507.6.1.2 | epc2x6powerports | GUDEADS-EPC2X6-MIB |
| 1.3.6.1.4.1.28507.6.1.2.2 | epc2x6portTable | GUDEADS-EPC2X6-MIB |
| 1.3.6.1.4.1.28507.6.1.2.2.1 | epc2x6portEntry | GUDEADS-EPC2X6-MIB |
| 1.3.6.1.4.1.28507.6.1.2.2.1.3 | epc2x6PortState | GUDEADS-EPC2X6-MIB |