GESINGLEUPS-MIB :: upsOutputShareCurrentgen

MIB Reference — IPNetwork Monitor · Updated October 05, 2026

All MIBs › GESINGLEUPS-MIB › upsOutputShareCurrentgen

upsOutputShareCurrentgen

Module: GESINGLEUPS-MIB

OID (symbolic): GESINGLEUPS-MIB::upsOutputShareCurrentgen

OID (numeric): 1.3.6.1.4.1.818.1.1.10.4.4.1.8

Node type: OBJECT-TYPE

Type: Integer32

Access: read-only

Description: In a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*)

What is upsOutputShareCurrentgen?

In a parallel UPS system, the portion of this unit's output current that is being exchanged with sibling UPSs rather than feeding the load directly; ideally this share current is zero since it represents wasted, undesired loading. PMAD (the parallel management logic) raises an alarm if share current exceeds a configured threshold, and single (non-parallel) UPS systems always report 'NA' here since the feature doesn't apply.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.818.1.1.10.4.4.1.8
snmpwalk -v2c -c public <target> GESINGLEUPS-MIB::upsOutputShareCurrentgen

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.818.1.1.10.4.4.1.8.1
snmpget -v2c -c public <target> GESINGLEUPS-MIB::upsOutputShareCurrentgen.1

Start monitoring GE Digital Energy single-unit UPS system with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the GESINGLEUPS-MIB::upsOutputShareCurrentgen OID value, configure state conditions and alerts, and monitor any GE Digital Energy single-unit UPS system from a single console.

OID Breakdown

Upper-level ancestors (13 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.818imvGE-PARALLELUPS
1.3.6.1.4.1.818.1geHardwareGE-PARALLELUPS
1.3.6.1.4.1.818.1.1geUPSGE-PARALLELUPS
1.3.6.1.4.1.818.1.1.10geGenericUPSGE-PARALLELUPS
1.3.6.1.4.1.818.1.1.10.4upsOutput_genGE-PARALLELUPS
1.3.6.1.4.1.818.1.1.10.4.4upsOutputTable_genGE-PARALLELUPS
1.3.6.1.4.1.818.1.1.10.4.4.1upsOutputEntry_genGE-PARALLELUPS
Numeric OIDNameModule
1.3.6.1.4.1.818.1.1.10.4.4.1.8upsOutputShareCurrentgenGESINGLEUPS-MIB