All MIBs › GESINGLEUPS-MIB › upsDiagnosticGlobalServiceCheckgen
upsDiagnosticGlobalServiceCheckgen
Module: GESINGLEUPS-MIB
OID (symbolic): GESINGLEUPS-MIB::upsDiagnosticGlobalServiceCheckgen
OID (numeric): 1.3.6.1.4.1.818.1.1.10.12.7
Node type: OBJECT-TYPE
Type: Integer32
Access: read-only
Description: The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*)
What is upsDiagnosticGlobalServiceCheckgen?
An aggregate remaining-lifetime countdown across the UPS's monitored critical components (battery, fans, DC and AC capacitors), decremented over time from supplier-defined defaults; when it reaches zero, a service-check warning is raised indicating the unit as a whole is due for inspection. Note: the source MIB reuses the identical per-component lifetime DESCRIPTION text verbatim for this object, so this explanation treats it as the combined/overall service-check indicator implied by its own name rather than one specific component.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.818.1.1.10.12.7 snmpwalk -v2c -c public <target> GESINGLEUPS-MIB::upsDiagnosticGlobalServiceCheckgen
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.818.1.1.10.12.7.1 snmpget -v2c -c public <target> GESINGLEUPS-MIB::upsDiagnosticGlobalServiceCheckgen.1
Start monitoring GE Digital Energy single-unit UPS system with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the GESINGLEUPS-MIB::upsDiagnosticGlobalServiceCheckgen OID value, configure state conditions and alerts, and monitor any GE Digital Energy single-unit UPS system from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.818 | imv | GE-PARALLELUPS |
| 1.3.6.1.4.1.818.1 | geHardware | GE-PARALLELUPS |
| 1.3.6.1.4.1.818.1.1 | geUPS | GE-PARALLELUPS |
| 1.3.6.1.4.1.818.1.1.10 | geGenericUPS | GE-PARALLELUPS |
| 1.3.6.1.4.1.818.1.1.10.12 | upsDiagnostic | GEPARALLELUPS-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.818.1.1.10.12.7 | upsDiagnosticGlobalServiceCheckgen | GESINGLEUPS-MIB |