All MIBs › ELTEK-GENERIC-MIB › systemNominalVoltage
systemNominalVoltage
Module: ELTEK-GENERIC-MIB
OID (symbolic): ELTEK-GENERIC-MIB::systemNominalVoltage
OID (numeric): 1.3.6.1.4.1.12148.7.2.1.4
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-only
Description: The nominal voltage rating. 12V/24V/48V/60V systems 0=48V 1=24V 2=12V 3=26V 4=60V
What is systemNominalVoltage?
Reports which nominal DC voltage class the plant is configured for: prs48v(0), prs24v(1), prs12v(2), prs26v(3), or prs60v(4); an admin checks this to know the expected battery/rectifier voltage range before interpreting other voltage readings on the same system.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.12148.7.2.1.4 snmpwalk -v2c -c public <target> ELTEK-GENERIC-MIB::systemNominalVoltage
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.12148.7.2.1.4.1 snmpget -v2c -c public <target> ELTEK-GENERIC-MIB::systemNominalVoltage.1
Start monitoring Eltek DC power-system control unit (site identity/trap config) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ELTEK-GENERIC-MIB::systemNominalVoltage OID value, configure state conditions and alerts, and monitor any Eltek DC power-system control unit (site identity/trap config) from a single console.
OID Breakdown
Upper-level ancestors (7 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.12148 | eltek | ELTEK-COMMON-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.12148.7 | eltekPlant | ELTEK-GENERIC-MIB |
| 1.3.6.1.4.1.12148.7.2 | dcSystem | ELTEK-GENERIC-MIB |
| 1.3.6.1.4.1.12148.7.2.1 | dcPlant | ELTEK-GENERIC-MIB |
| 1.3.6.1.4.1.12148.7.2.1.4 | systemNominalVoltage | ELTEK-GENERIC-MIB |