Module: ELTEK-GENERIC-MIB

OID (symbolic): ELTEK-GENERIC-MIB::batteryTempCompEnable

OID (numeric): 1.3.6.1.4.1.12148.7.3.8

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: Enable (0) or Disable (1) Battery Temperature Compensated output regulation mode

What is batteryTempCompEnable?

Toggles temperature-compensated float charging, where the charge voltage is automatically adjusted based on batteryTemp to avoid over- or under-charging as ambient temperature changes. Note: the SYNTAX defines disable(0)/enable(1), but the source DESCRIPTION text has the wording reversed ('Enable (0) or Disable (1)') — the SYNTAX numbering (1=enable, 0=disable) should be treated as authoritative, matching how the other on/off controls in this MIB are defined.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.12148.7.3.8
snmpwalk -v2c -c public <target> ELTEK-GENERIC-MIB::batteryTempCompEnable

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.12148.7.3.8.1
snmpget -v2c -c public <target> ELTEK-GENERIC-MIB::batteryTempCompEnable.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.12148.7.3.8.1 i <value>

Start monitoring Eltek DC power-system control unit (site identity/trap config) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ELTEK-GENERIC-MIB::batteryTempCompEnable OID value, configure state conditions and alerts, and monitor any Eltek DC power-system control unit (site identity/trap config) from a single console.

OID Breakdown

Upper-level ancestors (7 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.12148eltekELTEK-COMMON-MIB
Numeric OIDNameModule
1.3.6.1.4.1.12148.7eltekPlantELTEK-GENERIC-MIB
1.3.6.1.4.1.12148.7.3batteryELTEK-GENERIC-MIB
1.3.6.1.4.1.12148.7.3.8batteryTempCompEnableELTEK-GENERIC-MIB