All MIBs › ELTEK-GENERIC-MIB › alarmBatteryTestmodeEntered
alarmBatteryTestmodeEntered
Module: ELTEK-GENERIC-MIB
OID (symbolic): ELTEK-GENERIC-MIB::alarmBatteryTestmodeEntered
OID (numeric): 1.3.6.1.4.1.12148.7.7.1.19
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-only
Description: The system has lowered the battery charge voltage in order to discharge the batteries to a predefinend level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging.
What is alarmBatteryTestmodeEntered?
Indicates alarm(1) while the system is running a battery discharge test, during which it has intentionally lowered the charge voltage to discharge the batteries to a target level before resuming normal float charging — treat this as informational rather than a fault while active.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.12148.7.7.1.19 snmpwalk -v2c -c public <target> ELTEK-GENERIC-MIB::alarmBatteryTestmodeEntered
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.12148.7.7.1.19.1 snmpget -v2c -c public <target> ELTEK-GENERIC-MIB::alarmBatteryTestmodeEntered.1
Start monitoring Eltek DC power-system control unit (site identity/trap config) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ELTEK-GENERIC-MIB::alarmBatteryTestmodeEntered OID value, configure state conditions and alerts, and monitor any Eltek DC power-system control unit (site identity/trap config) from a single console.
OID Breakdown
Upper-level ancestors (7 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.12148 | eltek | ELTEK-COMMON-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.12148.7 | eltekPlant | ELTEK-GENERIC-MIB |
| 1.3.6.1.4.1.12148.7.7 | alarmGroup | ELTEK-GENERIC-MIB |
| 1.3.6.1.4.1.12148.7.7.1 | alarmWellknownAlarms | ELTEK-GENERIC-MIB |
| 1.3.6.1.4.1.12148.7.7.1.19 | alarmBatteryTestmodeEntered | ELTEK-GENERIC-MIB |