All MIBs › ELTEK-GENERIC-MIB › alarmBatteryDisconnectOpen
alarmBatteryDisconnectOpen
Module: ELTEK-GENERIC-MIB
OID (symbolic): ELTEK-GENERIC-MIB::alarmBatteryDisconnectOpen
OID (numeric): 1.3.6.1.4.1.12148.7.7.1.7
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-only
Description: The Battery Disconnect Contactor alarm
What is alarmBatteryDisconnectOpen?
Indicates alarm(1) when the main battery disconnect contactor has opened, meaning the battery bank is isolated from the DC bus and no longer providing backup; normal(0) means the battery is connected.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.12148.7.7.1.7 snmpwalk -v2c -c public <target> ELTEK-GENERIC-MIB::alarmBatteryDisconnectOpen
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.12148.7.7.1.7.1 snmpget -v2c -c public <target> ELTEK-GENERIC-MIB::alarmBatteryDisconnectOpen.1
Start monitoring Eltek DC power-system control unit (site identity/trap config) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ELTEK-GENERIC-MIB::alarmBatteryDisconnectOpen OID value, configure state conditions and alerts, and monitor any Eltek DC power-system control unit (site identity/trap config) from a single console.
OID Breakdown
Upper-level ancestors (7 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.12148 | eltek | ELTEK-COMMON-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.12148.7 | eltekPlant | ELTEK-GENERIC-MIB |
| 1.3.6.1.4.1.12148.7.7 | alarmGroup | ELTEK-GENERIC-MIB |
| 1.3.6.1.4.1.12148.7.7.1 | alarmWellknownAlarms | ELTEK-GENERIC-MIB |
| 1.3.6.1.4.1.12148.7.7.1.7 | alarmBatteryDisconnectOpen | ELTEK-GENERIC-MIB |