ELTEK-DISTRIBUTED-PLANT-MIB :: batteryTemp

MIB Reference — IPNetwork Monitor · Updated October 05, 2026

All MIBs › ELTEK-DISTRIBUTED-PLANT-MIB › batteryTemp

batteryTemp

Module: ELTEK-DISTRIBUTED-PLANT-MIB

OID (symbolic): ELTEK-DISTRIBUTED-PLANT-MIB::batteryTemp

OID (numeric): 1.3.6.1.4.1.12148.8.3.4

Node type: OBJECT-TYPE

Type: Integer32

Access: read-only

Description: The battery temperature

What is batteryTemp?

The measured battery temperature in tenths of a degree Celsius (e.g. 250 = 25.0 C). Sysadmins watch this because excess battery heat both accelerates aging and is a fire-safety concern; it also feeds the plant's temperature-compensated charging logic.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.12148.8.3.4
snmpwalk -v2c -c public <target> ELTEK-DISTRIBUTED-PLANT-MIB::batteryTemp

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.12148.8.3.4.1
snmpget -v2c -c public <target> ELTEK-DISTRIBUTED-PLANT-MIB::batteryTemp.1

Start monitoring Eltek distributed DC power plant/rectifier system with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ELTEK-DISTRIBUTED-PLANT-MIB::batteryTemp OID value, configure state conditions and alerts, and monitor any Eltek distributed DC power plant/rectifier system from a single console.

OID Breakdown

Upper-level ancestors (7 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.12148eltekELTEK-COMMON-MIB
Numeric OIDNameModule
1.3.6.1.4.1.12148.8eltekDistributedPlantELTEK-DISTRIBUTED-PLANT-MIB
1.3.6.1.4.1.12148.8.3batteryELTEK-DISTRIBUTED-PLANT-MIB
1.3.6.1.4.1.12148.8.3.4batteryTempELTEK-DISTRIBUTED-PLANT-MIB