ELTEK-DISTRIBUTED-PLANT-MIB :: batteryStartManualTest

MIB Reference — IPNetwork Monitor · Updated October 05, 2026

All MIBs › ELTEK-DISTRIBUTED-PLANT-MIB › batteryStartManualTest

batteryStartManualTest

Module: ELTEK-DISTRIBUTED-PLANT-MIB

OID (symbolic): ELTEK-DISTRIBUTED-PLANT-MIB::batteryStartManualTest

OID (numeric): 1.3.6.1.4.1.12148.8.3.15

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: This pushbutton will start a manual battery test if otherwise the system allows it.

What is batteryStartManualTest?

A pushbutton object for manually controlling a battery capacity test: setting starttest(1) begins a test discharge (if the system's normal safeguards allow it) and stoptest(2) ends it early. Reading it always returns pushbutton(0); this is how an admin triggers an on-demand battery health check.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.12148.8.3.15
snmpwalk -v2c -c public <target> ELTEK-DISTRIBUTED-PLANT-MIB::batteryStartManualTest

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.12148.8.3.15.1
snmpget -v2c -c public <target> ELTEK-DISTRIBUTED-PLANT-MIB::batteryStartManualTest.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.12148.8.3.15.1 i <value>

Start monitoring Eltek distributed DC power plant/rectifier system with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ELTEK-DISTRIBUTED-PLANT-MIB::batteryStartManualTest OID value, configure state conditions and alerts, and monitor any Eltek distributed DC power plant/rectifier system from a single console.

OID Breakdown

Upper-level ancestors (7 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.12148eltekELTEK-COMMON-MIB
Numeric OIDNameModule
1.3.6.1.4.1.12148.8eltekDistributedPlantELTEK-DISTRIBUTED-PLANT-MIB
1.3.6.1.4.1.12148.8.3batteryELTEK-DISTRIBUTED-PLANT-MIB
1.3.6.1.4.1.12148.8.3.15batteryStartManualTestELTEK-DISTRIBUTED-PLANT-MIB