ELTEK-DISTRIBUTED-PLANT-MIB :: batteryBanksSymmetry4enable

MIB Reference — IPNetwork Monitor · Updated October 05, 2026

All MIBs › ELTEK-DISTRIBUTED-PLANT-MIB › batteryBanksSymmetry4enable

batteryBanksSymmetry4enable

Module: ELTEK-DISTRIBUTED-PLANT-MIB

OID (symbolic): ELTEK-DISTRIBUTED-PLANT-MIB::batteryBanksSymmetry4enable

OID (numeric): 1.3.6.1.4.1.12148.8.3.19.3.1.11

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: When set to 'on' the the symmetry input is activated. when turned off, measuments for this input is turned off and the correcponding value will read 0 volts and the alarm flag will be turned off

What is batteryBanksSymmetry4enable?

Turns midpoint-voltage symmetry monitoring on or off for battery bank #4: enable(1) activates the measurement, disable(0) turns it off and forces the corresponding delta-voltage reading to 0 with its alarm flag cleared. Disable a bank's channel if it isn't physically wired to a symmetry sensor to avoid false alarms.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.12148.8.3.19.3.1.11
snmpwalk -v2c -c public <target> ELTEK-DISTRIBUTED-PLANT-MIB::batteryBanksSymmetry4enable

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.12148.8.3.19.3.1.11.1
snmpget -v2c -c public <target> ELTEK-DISTRIBUTED-PLANT-MIB::batteryBanksSymmetry4enable.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.12148.8.3.19.3.1.11.1 i <value>

Start monitoring Eltek distributed DC power plant/rectifier system with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ELTEK-DISTRIBUTED-PLANT-MIB::batteryBanksSymmetry4enable OID value, configure state conditions and alerts, and monitor any Eltek distributed DC power plant/rectifier system from a single console.

OID Breakdown

Upper-level ancestors (7 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.12148eltekELTEK-COMMON-MIB
Numeric OIDNameModule
1.3.6.1.4.1.12148.8eltekDistributedPlantELTEK-DISTRIBUTED-PLANT-MIB
1.3.6.1.4.1.12148.8.3batteryELTEK-DISTRIBUTED-PLANT-MIB
1.3.6.1.4.1.12148.8.3.19batteryBanksELTEK-DISTRIBUTED-PLANT-MIB
1.3.6.1.4.1.12148.8.3.19.3batteryBanksTableELTEK-DISTRIBUTED-PLANT-MIB
1.3.6.1.4.1.12148.8.3.19.3.1batteryBanksEntryELTEK-DISTRIBUTED-PLANT-MIB
1.3.6.1.4.1.12148.8.3.19.3.1.11batteryBanksSymmetry4enableELTEK-DISTRIBUTED-PLANT-MIB