EATON-EPDU-PU-MI-MIB :: lowCurrentThreshold10

MIB Reference — IPNetwork Monitor · Updated October 05, 2026

All MIBs › EATON-EPDU-PU-MI-MIB › lowCurrentThreshold10

lowCurrentThreshold10

Module: EATON-EPDU-PU-MI-MIB

OID (symbolic): EATON-EPDU-PU-MI-MIB::lowCurrentThreshold10

OID (numeric): 1.3.6.1.4.1.20677.3.1.1.5.10

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: Low current threshold channel 10

What is lowCurrentThreshold10?

Read-write Integer32 (0-100) setting the low-current alarm threshold, in amps, for measurement channel 10 on this ePDU. An admin lowers or raises this so the system flags an alarm if channel 10's measured current drops below it — useful for catching a failed load, tripped breaker, or disconnected device downstream.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.20677.3.1.1.5.10
snmpwalk -v2c -c public <target> EATON-EPDU-PU-MI-MIB::lowCurrentThreshold10

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.20677.3.1.1.5.10.1
snmpget -v2c -c public <target> EATON-EPDU-PU-MI-MIB::lowCurrentThreshold10.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.20677.3.1.1.5.10.1 i <value>

Start monitoring Eaton ePDU Power Unit Metered Input (blue display) PDU with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the EATON-EPDU-PU-MI-MIB::lowCurrentThreshold10 OID value, configure state conditions and alerts, and monitor any Eaton ePDU Power Unit Metered Input (blue display) PDU from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.20677pulizziEATON-EPDU-PU-MI-MIB
1.3.6.1.4.1.20677.3monitoredepduEATON-EPDU-PU-MI-MIB
1.3.6.1.4.1.20677.3.1epdum1EATON-EPDU-PU-MI-MIB
1.3.6.1.4.1.20677.3.1.1epdum11EATON-EPDU-PU-MI-MIB
1.3.6.1.4.1.20677.3.1.1.5lowCurrentThreshEATON-EPDU-PU-MI-MIB
1.3.6.1.4.1.20677.3.1.1.5.10lowCurrentThreshold10EATON-EPDU-PU-MI-MIB