EATON-EPDU-PU-MI-MIB :: chan11

MIB Reference — IPNetwork Monitor · Updated October 05, 2026

All MIBs › EATON-EPDU-PU-MI-MIB › chan11

chan11

Module: EATON-EPDU-PU-MI-MIB

OID (symbolic): EATON-EPDU-PU-MI-MIB::chan11

OID (numeric): 1.3.6.1.4.1.20677.3.1.1.3.11

Node type: OBJECT-TYPE

Type: Integer32

Access: read-only

Description: Current Measurement channel 11, 0.1 Amps RMS. A value of 57 means 5.7A.

What is chan11?

Read-only live RMS current reading for measurement channel 11 on this Eaton ePDU, reported in tenths of an amp — for example a returned value of 57 means 5.7 A on that channel. Monitoring tools poll it to track real-time load and to compare against the lowCurrentThreshold11/highCurrentThreshold11 alarm settings.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.20677.3.1.1.3.11
snmpwalk -v2c -c public <target> EATON-EPDU-PU-MI-MIB::chan11

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.20677.3.1.1.3.11.1
snmpget -v2c -c public <target> EATON-EPDU-PU-MI-MIB::chan11.1

Start monitoring Eaton ePDU Power Unit Metered Input (blue display) PDU with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the EATON-EPDU-PU-MI-MIB::chan11 OID value, configure state conditions and alerts, and monitor any Eaton ePDU Power Unit Metered Input (blue display) PDU from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.20677pulizziEATON-EPDU-PU-MI-MIB
1.3.6.1.4.1.20677.3monitoredepduEATON-EPDU-PU-MI-MIB
1.3.6.1.4.1.20677.3.1epdum1EATON-EPDU-PU-MI-MIB
1.3.6.1.4.1.20677.3.1.1epdum11EATON-EPDU-PU-MI-MIB
1.3.6.1.4.1.20677.3.1.1.3measurementsEATON-EPDU-PU-MI-MIB
1.3.6.1.4.1.20677.3.1.1.3.11chan11EATON-EPDU-PU-MI-MIB