EATON-ATS2-MIB :: ats2InputStatusDephasing

MIB Reference — IPNetwork Monitor · Updated October 02, 2026

All MIBs › EATON-ATS2-MIB › ats2InputStatusDephasing

ats2InputStatusDephasing

Module: EATON-ATS2-MIB

OID (symbolic): EATON-ATS2-MIB::ats2InputStatusDephasing

OID (numeric): 1.3.6.1.4.1.534.10.2.3.1.1

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-only

Description: The dephasing status in between Source 1 and Source 2.

What is ats2InputStatusDephasing?

This read-only OID reports whether the phase difference between Source 1 and Source 2 is normal(1) or outOfRange(2). A status of outOfRange flags a condition that could force a non-synchronized (gap) transfer between sources.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.534.10.2.3.1.1
snmpwalk -v2c -c public <target> EATON-ATS2-MIB::ats2InputStatusDephasing

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.534.10.2.3.1.1.1
snmpget -v2c -c public <target> EATON-ATS2-MIB::ats2InputStatusDephasing.1

Start monitoring Eaton automatic transfer switches with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the EATON-ATS2-MIB::ats2InputStatusDephasing OID value, configure state conditions and alerts, and monitor any Eaton automatic transfer switches from a single console.

OID Breakdown

Upper-level ancestors (8 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.534eatonEATON-OIDS
1.3.6.1.4.1.534.10stsEATON-OIDS
Numeric OIDNameModule
1.3.6.1.4.1.534.10.2ats2EATON-ATS2-MIB
1.3.6.1.4.1.534.10.2.3ats2StatusEATON-ATS2-MIB
1.3.6.1.4.1.534.10.2.3.1ats2InputStatusEATON-ATS2-MIB
1.3.6.1.4.1.534.10.2.3.1.1ats2InputStatusDephasingEATON-ATS2-MIB