EATON-ATS2-MIB :: ats2EnvRemoteTempUpperLimit

MIB Reference — IPNetwork Monitor · Updated October 02, 2026

All MIBs › EATON-ATS2-MIB › ats2EnvRemoteTempUpperLimit

ats2EnvRemoteTempUpperLimit

Module: EATON-ATS2-MIB

OID (symbolic): EATON-ATS2-MIB::ats2EnvRemoteTempUpperLimit

OID (numeric): 1.3.6.1.4.1.534.10.2.5.6

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: The Upper Limit of the EMP temperature; if ats2EnvRemoteTemp rises above this value, the ats2RemoteTempBad alarm will occur. This value should be greater than ats2EnvRemoteTempLowerLimit.

What is ats2EnvRemoteTempUpperLimit?

This OID sets the upper temperature threshold, in degrees Centigrade, above which the ATS raises a remote-temperature-bad alarm; it should be set higher than ats2EnvRemoteTempLowerLimit. Admins tune this to catch overheating conditions in the monitored equipment space.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.534.10.2.5.6
snmpwalk -v2c -c public <target> EATON-ATS2-MIB::ats2EnvRemoteTempUpperLimit

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.534.10.2.5.6.1
snmpget -v2c -c public <target> EATON-ATS2-MIB::ats2EnvRemoteTempUpperLimit.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.534.10.2.5.6.1 i <value>

Start monitoring Eaton automatic transfer switches with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the EATON-ATS2-MIB::ats2EnvRemoteTempUpperLimit OID value, configure state conditions and alerts, and monitor any Eaton automatic transfer switches from a single console.

OID Breakdown

Upper-level ancestors (8 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.534eatonEATON-OIDS
1.3.6.1.4.1.534.10stsEATON-OIDS
Numeric OIDNameModule
1.3.6.1.4.1.534.10.2ats2EATON-ATS2-MIB
1.3.6.1.4.1.534.10.2.5ats2EnvironmentEATON-ATS2-MIB
1.3.6.1.4.1.534.10.2.5.6ats2EnvRemoteTempUpperLimitEATON-ATS2-MIB