All MIBs › EATON-ATS2-MIB › ats2ConfigHysteresisVoltage
ats2ConfigHysteresisVoltage
Module: EATON-ATS2-MIB
OID (symbolic): EATON-ATS2-MIB::ats2ConfigHysteresisVoltage
OID (numeric): 1.3.6.1.4.1.534.10.2.4.12
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-only
Description: Hysteresis between loss point and comeback point. Unit is 1 V.
What is ats2ConfigHysteresisVoltage?
This read-only OID, in units of 1V, gives the configured hysteresis margin between the voltage-loss point and the voltage-comeback point. This prevents the ATS from rapidly flapping between sources when input voltage hovers right at a threshold.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.534.10.2.4.12 snmpwalk -v2c -c public <target> EATON-ATS2-MIB::ats2ConfigHysteresisVoltage
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.534.10.2.4.12.1 snmpget -v2c -c public <target> EATON-ATS2-MIB::ats2ConfigHysteresisVoltage.1
Start monitoring Eaton automatic transfer switches with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the EATON-ATS2-MIB::ats2ConfigHysteresisVoltage OID value, configure state conditions and alerts, and monitor any Eaton automatic transfer switches from a single console.
OID Breakdown
Upper-level ancestors (8 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.534 | eaton | EATON-OIDS |
| 1.3.6.1.4.1.534.10 | sts | EATON-OIDS |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.534.10.2 | ats2 | EATON-ATS2-MIB |
| 1.3.6.1.4.1.534.10.2.4 | ats2Config | EATON-ATS2-MIB |
| 1.3.6.1.4.1.534.10.2.4.12 | ats2ConfigHysteresisVoltage | EATON-ATS2-MIB |