outSwitchCtrl

Module: DIGIPDU-MIB

OID (symbolic): DIGIPDU-MIB::outSwitchCtrl

OID (numeric): 1.3.6.1.4.1.10456.3.3.3.1.5

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: This OID is provided for Outlet Status information.

'0' if the out is None.

'1' Switch Ctrl On.

'2' Switch Ctrl Off.

'3' Switch Ctrl Reboot.

'4' Switch Ctrl On Off.

What is outSwitchCtrl?

Write this object to remotely control the outlet: none(0), ctrl-on(1), ctrl-off(2), ctrl-reboot(3) or ctrl-on-off(4) -- the primary object used to remote power-cycle a device plugged into this outlet.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.10456.3.3.3.1.5
snmpwalk -v2c -c public <target> DIGIPDU-MIB::outSwitchCtrl

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.10456.3.3.3.1.5.1
snmpget -v2c -c public <target> DIGIPDU-MIB::outSwitchCtrl.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.10456.3.3.3.1.5.1 i <value>

Start monitoring Digi power distribution unit (PDU) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the DIGIPDU-MIB::outSwitchCtrl OID value, configure state conditions and alerts, and monitor any Digi power distribution unit (PDU) from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.10456digipduDIGIPDU-MIB
1.3.6.1.4.1.10456.3smartDIGIPDU-MIB
1.3.6.1.4.1.10456.3.3peripheralTablesDIGIPDU-MIB
1.3.6.1.4.1.10456.3.3.3outTableDIGIPDU-MIB
1.3.6.1.4.1.10456.3.3.3.1outEntryDIGIPDU-MIB
1.3.6.1.4.1.10456.3.3.3.1.5outSwitchCtrlDIGIPDU-MIB