Access: read-only

Description: Switch state of the outlet: 1 = Outlet is on 2 = Outlet is off 3 = Outlet is on, but will turn off after a delay 4 = Outlet is off, but will turn on after a delay 5 = Starting reboot cycle, outlet is on, but will go to the rebootOff(6) state after a delay 6 = Rebooting, outlet is off, but it will turn on after a delay 7 = Cannot get outlet state

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.21239.5.2.3.5.1.4
snmpwalk -v2c -c public <target> VERTIV-V5-MIB::pduOutletSwitchState

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.21239.5.2.3.5.1.4.1
snmpget -v2c -c public <target> VERTIV-V5-MIB::pduOutletSwitchState.1

SNMPv3 example:

snmpget -v3 -l authPriv -u snmpv3-user -a SHA -A "AuthPassword1" -x AES -X "PrivPassword1" <target> pduOutletSwitchState.1

Start monitoring Vertiv UPS units, Vertiv PDUs, Vertiv precision cooling/thermal management systems (identity/firmware/temperature status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the VERTIV-V5-MIB::pduOutletSwitchState OID value, configure state conditions and alerts, and monitor any Vertiv UPS units, Vertiv PDUs, Vertiv precision cooling/thermal management systems (identity/firmware/temperature status) from a single console.

OID Breakdown

Upper-level ancestors (10 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.21239geistGEIST-IMD-MIB
1.3.6.1.4.1.21239.5blackbirdGEIST-IMD-MIB
1.3.6.1.4.1.21239.5.2imdGEIST-IMD-MIB
1.3.6.1.4.1.21239.5.2.3pduGEIST-IMD-MIB
Numeric OIDNameModule
1.3.6.1.4.1.21239.5.2.3.5pduOutletSwitchTableVERTIV-V5-MIB
1.3.6.1.4.1.21239.5.2.3.5.1pduOutletSwitchEntryVERTIV-V5-MIB
1.3.6.1.4.1.21239.5.2.3.5.1.4pduOutletSwitchStateVERTIV-V5-MIB