Description: This object contains 8 bits of information about the current operational status of the UPS. The bits are encoded as follows:
BIT 7: 1=replace battery condition BIT 6: 1=low battery condition BIT 5: 1=overloaded output condition BIT 4: 1=on-battery mode of operation BIT 3: 1=on-line mode of operation BIT 2: 1=Smart Boost mode of operation (where applicable) BIT 1: 1=UPS shut down due to low battery, overload, or `sleep' mode BIT 0: 1=run time calibration running
Note that bit 0 is the low-order bit.
What is upsStatusOperational?
An 8-bit field of operational status flags, including bit 4 for on-battery mode, bit 3 for on-line mode, bit 6 for low battery, and bit 7 for replace-battery condition; an admin decodes this bitmask for a full operational snapshot rather than checking each condition separately.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.52.4.1.1.10.6.1.1.1 snmpwalk -v2c -c public <target> UPS2-MIB::upsStatusOperational
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.52.4.1.1.10.6.1.1.1.1 snmpget -v2c -c public <target> UPS2-MIB::upsStatusOperational.1
Start monitoring Cabletron Systems UPS product line, SmartUPS/MatrixUPS models (battery/input-output power/environmental status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the UPS2-MIB::upsStatusOperational OID value, configure state conditions and alerts, and monitor any Cabletron Systems UPS product line, SmartUPS/MatrixUPS models (battery/input-output power/environmental status) from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.52 | cabletron | Cabletron-MIB |
| 1.3.6.1.4.1.52.4 | mibs | CT-PRIORITY-QUEUING |
| 1.3.6.1.4.1.52.4.1 | ctron | CTRON-ISDN-CONFIGURATION-MIB |
| 1.3.6.1.4.1.52.4.1.1 | ctPhysical | CTRON-MIB-NAMES |
| 1.3.6.1.4.1.52.4.1.1.10 | ctUPS | CTRON-MIB-NAMES |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.52.4.1.1.10.6 | upsStatus | UPS2-MIB |
| 1.3.6.1.4.1.52.4.1.1.10.6.1 | upsStatusTable | UPS2-MIB |
| 1.3.6.1.4.1.52.4.1.1.10.6.1.1 | upsStatusEntry | UPS2-MIB |
| 1.3.6.1.4.1.52.4.1.1.10.6.1.1.1 | upsStatusOperational | UPS2-MIB |