UPS2-MIB :: upsStatusFault

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › UPS2-MIB › upsStatusFault

upsStatusFault

Module: UPS2-MIB

OID (symbolic): UPS2-MIB::upsStatusFault

OID (numeric): 1.3.6.1.4.1.52.4.1.1.10.6.1.1.2

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-only

Description: This object contains 8 bits of information about the current fault conditions of the UPS. The bits are encoded as follows:

BIT 7: 1=UPS fault - internal temperature has exceeded nominal limits BIT 6: 1=UPS fault - bypass relay (where applicable) malfunction BIT 5: 1=UPS fault - battery charger failure BIT 4: 1=UPS in shut down mode via `S' command BIT 3: 1=UPS in `sleep' mode via `@ddd' command BIT 2: 1=UPS fault - main relay malfunction BIT 1: 1=UPS unable to transfer to on-battery operation due to overload BIT 0: 1=UPS's output unpowered due to low battery shut down

Note that bit 0 is the low-order bit.

What is upsStatusFault?

An 8-bit field of fault flags, including bit 7 for over-temperature, bit 5 for battery charger failure, and bit 2 for main relay malfunction; an admin decodes this bitmask first when the UPS reports any fault condition, to see exactly which internal component failed.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.52.4.1.1.10.6.1.1.2
snmpwalk -v2c -c public <target> UPS2-MIB::upsStatusFault

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.52.4.1.1.10.6.1.1.2.1
snmpget -v2c -c public <target> UPS2-MIB::upsStatusFault.1

Start monitoring Cabletron Systems UPS product line, SmartUPS/MatrixUPS models (battery/input-output power/environmental status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the UPS2-MIB::upsStatusFault OID value, configure state conditions and alerts, and monitor any Cabletron Systems UPS product line, SmartUPS/MatrixUPS models (battery/input-output power/environmental status) from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.52cabletronCabletron-MIB
1.3.6.1.4.1.52.4mibsCT-PRIORITY-QUEUING
1.3.6.1.4.1.52.4.1ctronCTRON-ISDN-CONFIGURATION-MIB
1.3.6.1.4.1.52.4.1.1ctPhysicalCTRON-MIB-NAMES
1.3.6.1.4.1.52.4.1.1.10ctUPSCTRON-MIB-NAMES
Numeric OIDNameModule
1.3.6.1.4.1.52.4.1.1.10.6upsStatusUPS2-MIB
1.3.6.1.4.1.52.4.1.1.10.6.1upsStatusTableUPS2-MIB
1.3.6.1.4.1.52.4.1.1.10.6.1.1upsStatusEntryUPS2-MIB
1.3.6.1.4.1.52.4.1.1.10.6.1.1.2upsStatusFaultUPS2-MIB