All MIBs › UPS2-MIB › upsExtMeasAlarmStatus
upsExtMeasAlarmStatus
Module: UPS2-MIB
OID (symbolic): UPS2-MIB::upsExtMeasAlarmStatus
OID (numeric): 1.3.6.1.4.1.52.4.1.1.10.8.1.1.4
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-only
Description: This object contains 8 bits of information about the current alarm status of the External Measurement Unit. The bits are encoded as follows:
BIT 7: 1=Upper temperature limit exceeded BIT 6: 1=Lower temperature limit exceeded BIT 5: 1=Upper relative humidity limit exceeded BIT 4: 1=Lower relative humidity limit exceeded BIT 3: 1=Contact input channel #4 alarm state BIT 2: 1=Contact input channel #3 alarm state BIT 1: 1=Contact input channel #2 alarm state BIT 0: 1=Contact input channel #1 alarm state
Note that bit 0 is the low-order bit.
What is upsExtMeasAlarmStatus?
An 8-bit field reporting which External Measurement Unit alarm conditions are currently active — upper/lower temperature limits, upper/lower humidity limits, and each of the four contact input channels — letting an admin decode exactly which environmental threshold or contact triggered an alarm.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.52.4.1.1.10.8.1.1.4 snmpwalk -v2c -c public <target> UPS2-MIB::upsExtMeasAlarmStatus
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.52.4.1.1.10.8.1.1.4.1 snmpget -v2c -c public <target> UPS2-MIB::upsExtMeasAlarmStatus.1
Start monitoring Cabletron Systems UPS product line, SmartUPS/MatrixUPS models (battery/input-output power/environmental status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the UPS2-MIB::upsExtMeasAlarmStatus OID value, configure state conditions and alerts, and monitor any Cabletron Systems UPS product line, SmartUPS/MatrixUPS models (battery/input-output power/environmental status) from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.52 | cabletron | Cabletron-MIB |
| 1.3.6.1.4.1.52.4 | mibs | CT-PRIORITY-QUEUING |
| 1.3.6.1.4.1.52.4.1 | ctron | CTRON-ISDN-CONFIGURATION-MIB |
| 1.3.6.1.4.1.52.4.1.1 | ctPhysical | CTRON-MIB-NAMES |
| 1.3.6.1.4.1.52.4.1.1.10 | ctUPS | CTRON-MIB-NAMES |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.52.4.1.1.10.8 | upsExtMeas | UPS2-MIB |
| 1.3.6.1.4.1.52.4.1.1.10.8.1 | upsExtMeasTable | UPS2-MIB |
| 1.3.6.1.4.1.52.4.1.1.10.8.1.1 | upsExtMeasEntry | UPS2-MIB |
| 1.3.6.1.4.1.52.4.1.1.10.8.1.1.4 | upsExtMeasAlarmStatus | UPS2-MIB |