All MIBs › UPS2-MIB › upsAddlFuncsStatusFault
upsAddlFuncsStatusFault
Module: UPS2-MIB
OID (symbolic): UPS2-MIB::upsAddlFuncsStatusFault
OID (numeric): 1.3.6.1.4.1.52.4.1.1.10.9.1.1.6
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-only
Description: This object contains 8 bits of information about the current fault conditions of the UPS. The bits are encoded as follows:
BIT 7: reserved for future use BIT 6: reserved for future use BIT 5: reserved for future use BIT 4: 1=UPS fault - DC imbalance, UPS in bypass BIT 3: 1=UPS fault - output voltage select failure, UPS in bypass BIT 2: 1=UPS fault - bypass supply failure BIT 1: 1=UPS fault - Isolation Unit fan failure BIT 0: 1=UPS fault - Electronics Unit fan failure, UPS in bypass
Note that bit 0 is the low-order bit.
What is upsAddlFuncsStatusFault?
An 8-bit field of additional fault flags on higher-end UPS models, including DC imbalance, output voltage select failure, bypass supply failure, and fan failures, which an admin decodes to diagnose bypass- and cooling-related faults not covered by the base upsStatusFault object.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.52.4.1.1.10.9.1.1.6 snmpwalk -v2c -c public <target> UPS2-MIB::upsAddlFuncsStatusFault
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.52.4.1.1.10.9.1.1.6.1 snmpget -v2c -c public <target> UPS2-MIB::upsAddlFuncsStatusFault.1
Start monitoring Cabletron Systems UPS product line, SmartUPS/MatrixUPS models (battery/input-output power/environmental status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the UPS2-MIB::upsAddlFuncsStatusFault OID value, configure state conditions and alerts, and monitor any Cabletron Systems UPS product line, SmartUPS/MatrixUPS models (battery/input-output power/environmental status) from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.52 | cabletron | Cabletron-MIB |
| 1.3.6.1.4.1.52.4 | mibs | CT-PRIORITY-QUEUING |
| 1.3.6.1.4.1.52.4.1 | ctron | CTRON-ISDN-CONFIGURATION-MIB |
| 1.3.6.1.4.1.52.4.1.1 | ctPhysical | CTRON-MIB-NAMES |
| 1.3.6.1.4.1.52.4.1.1.10 | ctUPS | CTRON-MIB-NAMES |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.52.4.1.1.10.9 | upsAddlFuncs | UPS2-MIB |
| 1.3.6.1.4.1.52.4.1.1.10.9.1 | upsAddlFuncsTable | UPS2-MIB |
| 1.3.6.1.4.1.52.4.1.1.10.9.1.1 | upsAddlFuncsEntry | UPS2-MIB |
| 1.3.6.1.4.1.52.4.1.1.10.9.1.1.6 | upsAddlFuncsStatusFault | UPS2-MIB |