UPS2-MIB :: upsAddlFuncsStatusFault

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › UPS2-MIB › upsAddlFuncsStatusFault

upsAddlFuncsStatusFault

Module: UPS2-MIB

OID (symbolic): UPS2-MIB::upsAddlFuncsStatusFault

OID (numeric): 1.3.6.1.4.1.52.4.1.1.10.9.1.1.6

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-only

Description: This object contains 8 bits of information about the current fault conditions of the UPS. The bits are encoded as follows:

BIT 7: reserved for future use BIT 6: reserved for future use BIT 5: reserved for future use BIT 4: 1=UPS fault - DC imbalance, UPS in bypass BIT 3: 1=UPS fault - output voltage select failure, UPS in bypass BIT 2: 1=UPS fault - bypass supply failure BIT 1: 1=UPS fault - Isolation Unit fan failure BIT 0: 1=UPS fault - Electronics Unit fan failure, UPS in bypass

Note that bit 0 is the low-order bit.

What is upsAddlFuncsStatusFault?

An 8-bit field of additional fault flags on higher-end UPS models, including DC imbalance, output voltage select failure, bypass supply failure, and fan failures, which an admin decodes to diagnose bypass- and cooling-related faults not covered by the base upsStatusFault object.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.52.4.1.1.10.9.1.1.6
snmpwalk -v2c -c public <target> UPS2-MIB::upsAddlFuncsStatusFault

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.52.4.1.1.10.9.1.1.6.1
snmpget -v2c -c public <target> UPS2-MIB::upsAddlFuncsStatusFault.1

Start monitoring Cabletron Systems UPS product line, SmartUPS/MatrixUPS models (battery/input-output power/environmental status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the UPS2-MIB::upsAddlFuncsStatusFault OID value, configure state conditions and alerts, and monitor any Cabletron Systems UPS product line, SmartUPS/MatrixUPS models (battery/input-output power/environmental status) from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.52cabletronCabletron-MIB
1.3.6.1.4.1.52.4mibsCT-PRIORITY-QUEUING
1.3.6.1.4.1.52.4.1ctronCTRON-ISDN-CONFIGURATION-MIB
1.3.6.1.4.1.52.4.1.1ctPhysicalCTRON-MIB-NAMES
1.3.6.1.4.1.52.4.1.1.10ctUPSCTRON-MIB-NAMES
Numeric OIDNameModule
1.3.6.1.4.1.52.4.1.1.10.9upsAddlFuncsUPS2-MIB
1.3.6.1.4.1.52.4.1.1.10.9.1upsAddlFuncsTableUPS2-MIB
1.3.6.1.4.1.52.4.1.1.10.9.1.1upsAddlFuncsEntryUPS2-MIB
1.3.6.1.4.1.52.4.1.1.10.9.1.1.6upsAddlFuncsStatusFaultUPS2-MIB