UPS-MIB :: upsBypassNumLines

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsUPS-MIBupsBypassNumLines

upsBypassNumLines

Module: UPS-MIB

OID (symbolic): UPS-MIB::upsBypassNumLines

OID (numeric): 1.3.6.1.2.1.33.1.5.2

Node type: OBJECT-TYPE

Type: NonNegativeInteger

Access: read-only

Description: The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.

What is upsBypassNumLines?

This object indicates how many electrical lines in the UPS bypass circuit (alternative power path that bypasses the inverter) are currently in use. A bypass circuit allows utility power to directly feed the load when the UPS is in bypass mode. Facility engineers check this to verify that bypass capacity is appropriate for the protected equipment load.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.2.1.33.1.5.2
snmpwalk -v2c -c public <target> UPS-MIB::upsBypassNumLines

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.2.1.33.1.5.2.1
snmpget -v2c -c public <target> UPS-MIB::upsBypassNumLines.1

Start monitoring vendor-neutral, standards-based MIB, Uninterruptible Power Supply (UPS) systems (battery health/runtime/alarm status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the UPS-MIB::upsBypassNumLines OID value, configure state conditions and alerts, and monitor any vendor-neutral, standards-based MIB, Uninterruptible Power Supply (UPS) systems (battery health/runtime/alarm status) from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.2mgmtAXON-MIB
1.3.6.1.2.1mib_2AXON-MIB
Numeric OIDNameModule
1.3.6.1.2.1.33upsMIBUPS-MIB
1.3.6.1.2.1.33.1upsObjectsUPS-MIB
1.3.6.1.2.1.33.1.5upsBypassUPS-MIB
1.3.6.1.2.1.33.1.5.2upsBypassNumLinesUPS-MIB