SITEBOSS-420-STD-MIB :: esPointValueInt

MIB Reference — IPNetwork Monitor · Updated September 21, 2026

All MIBs › SITEBOSS-420-STD-MIB › esPointValueInt

esPointValueInt

Module: SITEBOSS-420-STD-MIB

OID (symbolic): SITEBOSS-420-STD-MIB::esPointValueInt

OID (numeric): 1.3.6.1.4.1.3052.42.1.1.1.1.6

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: A read-only number referring to the value of a point on an EventSensor.

If the point class is temperature, then this object is the temperature in its configured scale (default is Fahrenheit).

If the point class is contact closure or relay, then this object is either 0 (open) or 1 (closed).

If the point class is humidity, then this object is the percent relative humidity.

If the point class is analog input, then this object is the signed input value in tenths of the configured units.

If the point class is relay, then this object is either 1 (active a.k.a. energized) or 0 (inactive a.k.a. de-energized). This object cannot be used to control the relay (use esPointInEventState for that).

What is esPointValueInt?

The current numeric reading of a point, whose units depend on the point class: degrees in the configured scale for temperature, 0/1 for open/closed contact closures, percent for humidity, tenths of a configured unit for analog inputs, and 0/1 for relay state. Despite the read-write MAX-ACCESS, the description notes it is read-only in practice and relays must be controlled through esPointInEventState instead.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.3052.42.1.1.1.1.6
snmpwalk -v2c -c public <target> SITEBOSS-420-STD-MIB::esPointValueInt

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.3052.42.1.1.1.1.6.1
snmpget -v2c -c public <target> SITEBOSS-420-STD-MIB::esPointValueInt.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.3052.42.1.1.1.1.6.1 i <value>

SNMPv3 example:

snmpget -v3 -l authPriv -u snmpv3-user -a SHA -A "AuthPassword1" -x AES -X "PrivPassword1" <target> esPointValueInt.1

Start monitoring Asentria SiteBoss 420 remote site monitoring unit (environmental sensor point/alarm status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the SITEBOSS-420-STD-MIB::esPointValueInt OID value, configure state conditions and alerts, and monitor any Asentria SiteBoss 420 remote site monitoring unit (environmental sensor point/alarm status) from a single console.

OID Breakdown

Upper-level ancestors (7 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.3052asentriaASENTRIA-ROOT-MIB
Numeric OIDNameModule
1.3.6.1.4.1.3052.42s420SITEBOSS-420-STD-MIB
1.3.6.1.4.1.3052.42.1statusSITEBOSS-420-STD-MIB
1.3.6.1.4.1.3052.42.1.1eventSensorStatusSITEBOSS-420-STD-MIB
1.3.6.1.4.1.3052.42.1.1.1esPointTableSITEBOSS-420-STD-MIB
1.3.6.1.4.1.3052.42.1.1.1.1esPointEntrySITEBOSS-420-STD-MIB
1.3.6.1.4.1.3052.42.1.1.1.1.6esPointValueIntSITEBOSS-420-STD-MIB