PM-MIB :: pmPowerMgmtPDUTablePowerControl

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › PM-MIB › pmPowerMgmtPDUTablePowerControl

pmPowerMgmtPDUTablePowerControl

Module: PM-MIB

OID (symbolic): PM-MIB::pmPowerMgmtPDUTablePowerControl

OID (numeric): 1.3.6.1.4.1.10418.17.2.5.3.1.90

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: A set value of power*(2-4) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is sent to PDU. powerOff(3) = when SET the power Off command is sent to PDU. powerCycle(4)=when SET the power cycle command is sent to PDU. Returns 0 if not supported.

What is pmPowerMgmtPDUTablePowerControl?

A control object for this whole PDU: a GET always returns noAction(1); setting powerOn(2), powerOff(3), or powerCycle(4) sends that command to every outlet on the PDU at once (0 if unsupported). Used for emergency all-outlet shutdown/restart of an entire power strip rather than one outlet at a time.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.10418.17.2.5.3.1.90
snmpwalk -v2c -c public <target> PM-MIB::pmPowerMgmtPDUTablePowerControl

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.10418.17.2.5.3.1.90.1
snmpget -v2c -c public <target> PM-MIB::pmPowerMgmtPDUTablePowerControl.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.10418.17.2.5.3.1.90.1 i <value>

Start monitoring Avocent PM-PDU intelligent power distribution units with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the PM-MIB::pmPowerMgmtPDUTablePowerControl OID value, configure state conditions and alerts, and monitor any Avocent PM-PDU intelligent power distribution units from a single console.

OID Breakdown

Upper-level ancestors (7 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.10418dellDELLRCSG2-TRAP-MIB
Numeric OIDNameModule
1.3.6.1.4.1.10418.17pmPM-MIB
1.3.6.1.4.1.10418.17.2pmManagementPM-MIB
1.3.6.1.4.1.10418.17.2.5pmPowerMgmtPM-MIB
1.3.6.1.4.1.10418.17.2.5.3pmPowerMgmtPDUTablePM-MIB
1.3.6.1.4.1.10418.17.2.5.3.1pmPowerMgmtPDUTableEntryPM-MIB
1.3.6.1.4.1.10418.17.2.5.3.1.90pmPowerMgmtPDUTablePowerControlPM-MIB