HMRING-MGMT-SNMP-MIB :: hmRingCplCouplingLinks

MIB Reference — IPNetwork Monitor · Updated October 05, 2026

All MIBs › HMRING-MGMT-SNMP-MIB › hmRingCplCouplingLinks

hmRingCplCouplingLinks

Module: HMRING-MGMT-SNMP-MIB

OID (symbolic): HMRING-MGMT-SNMP-MIB::hmRingCplCouplingLinks

OID (numeric): 1.3.6.1.4.1.248.14.5.2.1.16

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: Maximum coupling links between two coupled rings in case of a failure in one of the coupled rings.

If there is no connection starting from the switch in slave or local operational state over the route of the coupled rings or nets to oneself the slave or the local mode want to set the coupling port in forwarding after a timeout period.

basicRedundancy(1) prevents the slave or the local mode from setting its coupling port into forwarding in case of the described failure. In this case the segment which is connected to this coupling port is unreachable until the failure is eliminated.

In extendedRedundancy(2) the coupling port and the partner coupling port are allowed to be in forwarding.

What is hmRingCplCouplingLinks?

Controls how aggressively the coupling port is allowed to reopen after a failure elsewhere in the coupled rings: basicRedundancy(1) keeps the segment behind this coupling port isolated until the original fault is fixed, while extendedRedundancy(2) lets both the coupling port and its partner forward traffic to restore connectivity sooner. An admin would choose extendedRedundancy on a network where reachability after a fault matters more than avoiding a brief loop risk.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.248.14.5.2.1.16
snmpwalk -v2c -c public <target> HMRING-MGMT-SNMP-MIB::hmRingCplCouplingLinks

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.248.14.5.2.1.16.1
snmpget -v2c -c public <target> HMRING-MGMT-SNMP-MIB::hmRingCplCouplingLinks.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.248.14.5.2.1.16.1 i <value>

Start monitoring Hirschmann industrial Ethernet switches with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the HMRING-MGMT-SNMP-MIB::hmRingCplCouplingLinks OID value, configure state conditions and alerts, and monitor any Hirschmann industrial Ethernet switches from a single console.

OID Breakdown

Upper-level ancestors (8 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.248hirschmannHIRSCHMANN-GENERIC-ERROR-MIB
1.3.6.1.4.1.248.14hmConfigurationHMPRIV-MGMT-SNMP-MIB
Numeric OIDNameModule
1.3.6.1.4.1.248.14.5hmRingRedundancyHMRING-MGMT-SNMP-MIB
1.3.6.1.4.1.248.14.5.2hmRingCouplingTableHMRING-MGMT-SNMP-MIB
1.3.6.1.4.1.248.14.5.2.1hmRingCouplingEntryHMRING-MGMT-SNMP-MIB
1.3.6.1.4.1.248.14.5.2.1.16hmRingCplCouplingLinksHMRING-MGMT-SNMP-MIB