EES-POWER-MIB :: systemStatus

MIB Reference — IPNetwork Monitor · Updated October 05, 2026

All MIBs › EES-POWER-MIB › systemStatus

systemStatus

Module: EES-POWER-MIB

OID (symbolic): EES-POWER-MIB::systemStatus

OID (numeric): 1.3.6.1.4.1.6302.2.1.2.1

Node type: OBJECT-TYPE

Type: Status

Access: read-only

Description: Status of the complete plant (highest alarm). One of (1) unknown - status has not yet been defined (2) normal - there are no activated alarms (3) observation - OA, lowest level of 'abnormal' status (4) warning - A3 (5) minor - MA (6) major - CA, highest level of 'abnormal' status (7) unmanaged (8) restricted (9) testing (10) disabled

What is systemStatus?

Read-only status code (Status TC) giving the plant's overall highest active alarm severity, from normal(2) through observation/warning/minor to major(6), plus administrative states like unmanaged(7) or disabled(10). Poll this first for a one-glance health summary of the whole DC power plant before drilling into individual battery or input alarms.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.6302.2.1.2.1
snmpwalk -v2c -c public <target> EES-POWER-MIB::systemStatus

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.6302.2.1.2.1.1
snmpget -v2c -c public <target> EES-POWER-MIB::systemStatus.1

Start monitoring Emerson Energy Systems (EES) DC power/rectifier system with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the EES-POWER-MIB::systemStatus OID value, configure state conditions and alerts, and monitor any Emerson Energy Systems (EES) DC power/rectifier system from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.6302eesEES-POWER-MIB
1.3.6.1.4.1.6302.2_pysmi_globalEES-POWER-MIB
1.3.6.1.4.1.6302.2.1powerMIBEES-POWER-MIB
1.3.6.1.4.1.6302.2.1.2systemEES-POWER-MIB
1.3.6.1.4.1.6302.2.1.2.1systemStatusEES-POWER-MIB