CPS6000-MIB :: cps6000Sc1Lsp

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsCPS6000-MIBcps6000Sc1Lsp

cps6000Sc1Lsp

Module: CPS6000-MIB

OID (symbolic): CPS6000-MIB::cps6000Sc1Lsp

OID (numeric): 1.3.6.1.4.1.10520.2.1.1.10.9

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: Lower Temperature Slope/Cell (mV/C/Cell)

What is cps6000Sc1Lsp?

This read-write Integer32, in mV/C/Cell, sets the voltage compensation slope applied per battery cell for temperatures below the nominal threshold cps6000Sc1Ntt. An administrator configures it to the battery manufacturer's specified cold-temperature compensation slope. For example, a value of -3 mV/C/Cell would raise per-cell charge voltage by 3mV for every degree the temperature drops below nominal.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.10520.2.1.1.10.9
snmpwalk -v2c -c public <target> CPS6000-MIB::cps6000Sc1Lsp

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.10520.2.1.1.10.9.1
snmpget -v2c -c public <target> CPS6000-MIB::cps6000Sc1Lsp.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.10520.2.1.1.10.9.1 i <value>

Start monitoring CyberPower CPS6000-series UPS with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPS6000-MIB::cps6000Sc1Lsp OID value, configure state conditions and alerts, and monitor any CyberPower CPS6000-series UPS from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.10520tepsCPS6000-MIB
1.3.6.1.4.1.10520.2controllermibsCPS6000-MIB
1.3.6.1.4.1.10520.2.1releaseCPS6000-MIB
1.3.6.1.4.1.10520.2.1.1cps6000CPS6000-MIB
1.3.6.1.4.1.10520.2.1.1.10cps6000Sc1CPS6000-MIB
1.3.6.1.4.1.10520.2.1.1.10.9cps6000Sc1LspCPS6000-MIB