CPS6000-MIB :: cps6000Gm1Bcl

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsCPS6000-MIBcps6000Gm1Bcl

cps6000Gm1Bcl

Module: CPS6000-MIB

OID (symbolic): CPS6000-MIB::cps6000Gm1Bcl

OID (numeric): 1.3.6.1.4.1.10520.2.1.1.5.9

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: Boost Current Limit (%)

What is cps6000Gm1Bcl?

This read-write Integer32, constrained to 30-110 percent, caps the output current the rectifier plant delivers while in boost mode, as a percentage of rated capacity. An administrator may raise it above the float limit, since boost charging is expected to draw more current to recharge batteries quickly. For example, setting cps6000Gm1Bcl to 100 allows the plant to deliver full rated current during a boost recharge cycle.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.10520.2.1.1.5.9
snmpwalk -v2c -c public <target> CPS6000-MIB::cps6000Gm1Bcl

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.10520.2.1.1.5.9.1
snmpget -v2c -c public <target> CPS6000-MIB::cps6000Gm1Bcl.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.10520.2.1.1.5.9.1 i <value>

Start monitoring CyberPower CPS6000-series UPS with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPS6000-MIB::cps6000Gm1Bcl OID value, configure state conditions and alerts, and monitor any CyberPower CPS6000-series UPS from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.10520tepsCPS6000-MIB
1.3.6.1.4.1.10520.2controllermibsCPS6000-MIB
1.3.6.1.4.1.10520.2.1releaseCPS6000-MIB
1.3.6.1.4.1.10520.2.1.1cps6000CPS6000-MIB
1.3.6.1.4.1.10520.2.1.1.5cps6000Gm1CPS6000-MIB
1.3.6.1.4.1.10520.2.1.1.5.9cps6000Gm1BclCPS6000-MIB