CPS6000-MIB :: cps6000Cp1Rth

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsCPS6000-MIBcps6000Cp1Rth

cps6000Cp1Rth

Module: CPS6000-MIB

OID (symbolic): CPS6000-MIB::cps6000Cp1Rth

OID (numeric): 1.3.6.1.4.1.10520.2.1.1.7.8

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: Low Voltage Reconnect (mV)

What is cps6000Cp1Rth?

This read-write Integer32, constrained to 22000-27000 mV, sets the voltage at which a previously disconnected Cp1 load will be reconnected once the source has recovered, working with cps6000Cp1Dth. An administrator configures it above the disconnect threshold to avoid rapid reconnect/disconnect cycling. For example, setting cps6000Cp1Rth to 24000 waits until the source recovers to 24V before restoring the load.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.10520.2.1.1.7.8
snmpwalk -v2c -c public <target> CPS6000-MIB::cps6000Cp1Rth

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.10520.2.1.1.7.8.1
snmpget -v2c -c public <target> CPS6000-MIB::cps6000Cp1Rth.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.10520.2.1.1.7.8.1 i <value>

Start monitoring CyberPower CPS6000-series UPS with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPS6000-MIB::cps6000Cp1Rth OID value, configure state conditions and alerts, and monitor any CyberPower CPS6000-series UPS from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.10520tepsCPS6000-MIB
1.3.6.1.4.1.10520.2controllermibsCPS6000-MIB
1.3.6.1.4.1.10520.2.1releaseCPS6000-MIB
1.3.6.1.4.1.10520.2.1.1cps6000CPS6000-MIB
1.3.6.1.4.1.10520.2.1.1.7cps6000Cp1CPS6000-MIB
1.3.6.1.4.1.10520.2.1.1.7.8cps6000Cp1RthCPS6000-MIB