CPS6000-MIB :: cps6000Cp1Dth

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsCPS6000-MIBcps6000Cp1Dth

cps6000Cp1Dth

Module: CPS6000-MIB

OID (symbolic): CPS6000-MIB::cps6000Cp1Dth

OID (numeric): 1.3.6.1.4.1.10520.2.1.1.7.7

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: Low Voltage Disconnect (mV)

What is cps6000Cp1Dth?

This read-write Integer32, constrained to 20000-25000 mV, sets the input voltage threshold below which the Cp1 converter bank will disconnect its load to protect against a deep battery discharge. An administrator sets it to a value that preserves battery life while still riding through short dips. For example, setting cps6000Cp1Dth to 21000 disconnects the load once the source voltage falls to 21V.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.10520.2.1.1.7.7
snmpwalk -v2c -c public <target> CPS6000-MIB::cps6000Cp1Dth

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.10520.2.1.1.7.7.1
snmpget -v2c -c public <target> CPS6000-MIB::cps6000Cp1Dth.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.10520.2.1.1.7.7.1 i <value>

Start monitoring CyberPower CPS6000-series UPS with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPS6000-MIB::cps6000Cp1Dth OID value, configure state conditions and alerts, and monitor any CyberPower CPS6000-series UPS from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.10520tepsCPS6000-MIB
1.3.6.1.4.1.10520.2controllermibsCPS6000-MIB
1.3.6.1.4.1.10520.2.1releaseCPS6000-MIB
1.3.6.1.4.1.10520.2.1.1cps6000CPS6000-MIB
1.3.6.1.4.1.10520.2.1.1.7cps6000Cp1CPS6000-MIB
1.3.6.1.4.1.10520.2.1.1.7.7cps6000Cp1DthCPS6000-MIB