GEIST-V4-MIB :: tempSensorTemp

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsGEIST-V4-MIBtempSensorTemp

tempSensorTemp

Module: GEIST-V4-MIB

OID (symbolic): GEIST-V4-MIB::tempSensorTemp

OID (numeric): 1.3.6.1.4.1.21239.5.1.4.1.5

Node type: OBJECT-TYPE

Type: Integer32

Access: read-only

Description: Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo

What is tempSensorTemp?

This read-only Integer32 (-40 to 200, in tenths of a degree) is the current temperature reading from this remote temperature sensor, in whichever unit temperatureUnits selects. Use it the same way as the base unit's internalTemp, but for a remote probe placed elsewhere in the rack or room.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.21239.5.1.4.1.5
snmpwalk -v2c -c public <target> GEIST-V4-MIB::tempSensorTemp

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.21239.5.1.4.1.5.1
snmpget -v2c -c public <target> GEIST-V4-MIB::tempSensorTemp.1

Start monitoring Geist rack PDU / environmental monitoring appliance (V4 generation) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the GEIST-V4-MIB::tempSensorTemp OID value, configure state conditions and alerts, and monitor any Geist rack PDU / environmental monitoring appliance (V4 generation) from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.21239geistGEIST-V4-MIB
1.3.6.1.4.1.21239.5blackbirdGEIST-V4-MIB
1.3.6.1.4.1.21239.5.1bb100GEIST-V4-MIB
1.3.6.1.4.1.21239.5.1.4tempSensorTableGEIST-V4-MIB
1.3.6.1.4.1.21239.5.1.4.1tempSensorEntryGEIST-V4-MIB
1.3.6.1.4.1.21239.5.1.4.1.5tempSensorTempGEIST-V4-MIB