-- ---------------------------------------------------------------------- -- -- Copyright (c) 2006 by Sinetica Corporation Ltd. -- -- Filename: RMS-C_SNMPv1_main.mib -- -- Author: Adrian Moruz -- -- Description: SNMPv1 MIB for the Knuerr RMS Compact -- -- $Id: RMS-C_SNMPv1_main.mib,v 1.1 2006/10/11 11:23:04 adrian.moruz Exp $ -- -- $Name: $ -- -- $Log: RMS-C_SNMPv1_main.mib,v $ -- Revision 1.1 2006/10/11 11:23:04 adrian.moruz -- Created from RMS-C_SNMPv1.mib v1.2 to separate the different trap enterprise groups into separate MIBs -- -- -- ---------------------------------------------------------------------- RMS-COMPACT-SNMPv1-MAIN-MIB DEFINITIONS ::= BEGIN -- {{{ Imports -- OBJECT-TYPE, Counter32, Unsigned32, IMPORTS TRAP-TYPE FROM RFC-1215 sysDescr, sysName, DisplayString FROM RFC1213-MIB OBJECT-TYPE FROM RFC-1212 enterprises FROM RFC1155-SMI ; -- }}} sinetica OBJECT IDENTIFIER ::= { enterprises 3711 } rms-compact OBJECT IDENTIFIER ::= { sinetica 15 } rms-compact1 OBJECT IDENTIFIER ::= { rms-compact 1 } rms-cObjects OBJECT IDENTIFIER ::= { rms-compact1 1 } -- {{{ rms-cObjects rms-cEnviroment OBJECT IDENTIFIER ::= { rms-cObjects 1 } rms-cContact OBJECT IDENTIFIER ::= { rms-cObjects 2 } rms-cOutput OBJECT IDENTIFIER ::= { rms-cObjects 3 } -- }}} -- {{{ rms-cTemp group rms-cTemp1 OBJECT IDENTIFIER ::= { rms-cEnviroment 1 } rms-cHumid1 OBJECT IDENTIFIER ::= { rms-cEnviroment 2 } rms-cTemp2 OBJECT IDENTIFIER ::= { rms-cEnviroment 3 } rms-cHumid2 OBJECT IDENTIFIER ::= { rms-cEnviroment 4 } -- }}} -- {{{ rms-cTemp rms-cTemp1EnableMonitoring OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting to one enables monitoring of Temperature" ::= { rms-cTemp1 1 } rms-cTemp1Name OBJECT-TYPE SYNTAX DisplayString (SIZE(0..47)) ACCESS read-write STATUS mandatory DESCRIPTION "The name of the temperature reading" ::= { rms-cTemp1 2 } rms-cTemp1CalibrationOffset OBJECT-TYPE SYNTAX INTEGER (-100..100) ACCESS read-write STATUS mandatory DESCRIPTION "Calibration offset in 0.1 degrees" ::= { rms-cTemp1 3 } rms-cTemp1Current OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-only STATUS mandatory DESCRIPTION "The current temperature reading in 0.1%" ::= { rms-cTemp1 4 } rms-cTemp1Thresholds OBJECT IDENTIFIER ::= { rms-cTemp1 5 } rms-cTemp1OFFtoONtraps OBJECT IDENTIFIER ::= { rms-cTemp1 6 } rms-cTemp1OFFtoONrepeatTimers OBJECT IDENTIFIER ::= { rms-cTemp1 7 } rms-cTemp1ONtoOFFtraps OBJECT IDENTIFIER ::= { rms-cTemp1 8 } rms-cTemp1ONtoOFFrepeatTimers OBJECT IDENTIFIER ::= { rms-cTemp1 9 } -- {{{ rms-cTempThresholds rms-cTemp1LowerControlLevel OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-write STATUS mandatory DESCRIPTION "The Lower Limit temperature threshold in 0.1 degrees" ::= { rms-cTemp1Thresholds 1 } rms-cTemp1LowerWarningLevel OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-write STATUS mandatory DESCRIPTION "The Lower Control temperature threshold in 0.1 degrees" ::= { rms-cTemp1Thresholds 2 } rms-cTemp1UpperWarningLevel OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-write STATUS mandatory DESCRIPTION "The Upper Control temperature threshold in 0.1 degrees" ::= { rms-cTemp1Thresholds 3 } rms-cTemp1UpperControlLevel OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-write STATUS mandatory DESCRIPTION "The Upper Limit temperature threshold in 0.1 degrees" ::= { rms-cTemp1Thresholds 4 } -- }}} -- {{{ rms-cTempOFFtoONtraps rms-cTemp1OFFtoONtrapLCL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cTemp1OFFtoONtraps 1 } rms-cTemp1OFFtoONontrapLWL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cTemp1OFFtoONtraps 2 } rms-cTemp1OFFtoONtrapUWL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cTemp1OFFtoONtraps 3 } rms-cTemp1OFFtoONtrapUCL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cTemp1OFFtoONtraps 4 } -- }}} -- {{{ rms-cTempOFFtoONrepeatTimers rms-cTemp1OFFtoONrepLCL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in minutes" ::= { rms-cTemp1OFFtoONrepeatTimers 1 } rms-cTemp1OFFtoONrepLWL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in minutes" ::= { rms-cTemp1OFFtoONrepeatTimers 2 } rms-cTemp1OFFtoONrepUWL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in minutes" ::= { rms-cTemp1OFFtoONrepeatTimers 3 } rms-cTemp1OFFtoONrepUCL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in minutes" ::= { rms-cTemp1OFFtoONrepeatTimers 4 } -- }}} -- {{{ rms-cTempONtoOFFtraps rms-cTemp1ONtoOFFtrapLCL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cTemp1ONtoOFFtraps 1 } rms-cTemp1ONtoOFFtrapLWL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cTemp1ONtoOFFtraps 2 } rms-cTemp1ONtoOFFtrapUWL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cTemp1ONtoOFFtraps 3 } rms-cTemp1ONtoOFFtrapUCL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cTemp1ONtoOFFtraps 4 } -- }}} -- {{{ rms-cTempONtoOFFrepeatTimers rms-cTemp1ONtoOFFrepLCL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cTemp1ONtoOFFrepeatTimers 1 } rms-cTemp1ONtoOFFrepLWL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cTemp1ONtoOFFrepeatTimers 2 } rms-cTemp1ONtoOFFrepUWL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cTemp1ONtoOFFrepeatTimers 3 } rms-cTemp1ONtoOFFrepUCL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cTemp1ONtoOFFrepeatTimers 4 } -- }}} rms-cTemp1LowControlLimitAlarm TRAP-TYPE ENTERPRISE rms-cTemp1 VARIABLES { sysDescr, sysName, rms-cTemp1Name, rms-cTemp1LowerControlLevel } DESCRIPTION "Temperature is below the low control limit." --#TYPE "Temperature 1 below lower control limit" --#SUMMARY "Temperature %s below %d in %s at %s" --#ARGUMENTS {2,3,0,1} --#SEVERITY MAJOR --#TIMEINDEX 4 --#STATE NONOPERATIONAL ::= 101 rms-cTemp1LowWarningLimitAlarm TRAP-TYPE ENTERPRISE rms-cTemp1 VARIABLES { sysDescr, sysName, rms-cTemp1Name, rms-cTemp1LowerWarningLevel } DESCRIPTION "Temperature is below the low warning limit." --#TYPE "Temperature 1 below lower warning limit" --#SUMMARY "Temperature %s below %d in %s at %s" --#ARGUMENTS {2,3,0,1} --#SEVERITY MINOR --#TIMEINDEX 4 --#STATE NONOPERATIONAL ::= 102 rms-cTemp1HighWarningLimitAlarm TRAP-TYPE ENTERPRISE rms-cTemp1 VARIABLES { sysDescr, sysName, rms-cTemp1Name, rms-cTemp1UpperWarningLevel } DESCRIPTION "Temperature is over the high warning limit." --#TYPE "Temperature 1 above high warning limit" --#SUMMARY "Temperature %s above %d in %s at %s" --#ARGUMENTS {2,3,0,1} --#SEVERITY MINOR --#TIMEINDEX 4 --#STATE NONOPERATIONAL ::= 103 rms-cTemp1HighControlLimitAlarm TRAP-TYPE ENTERPRISE rms-cTemp1 VARIABLES { sysDescr, sysName, rms-cTemp1Name, rms-cTemp1UpperControlLevel } DESCRIPTION "Temperature is over the high control limit." --#TYPE "Temperature 1 above high control limit" --#SUMMARY "Temperature %s above %d in %s at %s" --#ARGUMENTS {2,3,0,1} --#SEVERITY MAJOR --#TIMEINDEX 4 --#STATE NONOPERATIONAL ::= 104 rms-cTemp1LowControlLimitNormal TRAP-TYPE ENTERPRISE rms-cTemp1 VARIABLES { sysDescr, sysName, rms-cTemp1Name, rms-cTemp1LowerControlLevel } DESCRIPTION "Temperature is inside the low control limit." --#TYPE "Temperature 1 above lower control limit" --#SUMMARY "Temperature %s above %d in %s at %s" --#ARGUMENTS {2,3,0,1} --#SEVERITY INFORMATIONAL --#TIMEINDEX 4 --#STATE NONOPERATIONAL ::= 105 rms-cTemp1LowWarningLimitNormal TRAP-TYPE ENTERPRISE rms-cTemp1 VARIABLES { sysDescr, sysName, rms-cTemp1Name, rms-cTemp1LowerWarningLevel } DESCRIPTION "Temperature is inside the low warning limit." --#TYPE "Temperature 1 above lower warning limit" --#SUMMARY "Temperature %s above %d in %s at %s" --#ARGUMENTS {2,3,0,1} --#SEVERITY INFORMATIONAL --#TIMEINDEX 4 --#STATE NONOPERATIONAL ::= 106 rms-cTemp1HighWarningLimitNormal TRAP-TYPE ENTERPRISE rms-cTemp1 VARIABLES { sysDescr, sysName, rms-cTemp1Name, rms-cTemp1UpperWarningLevel } DESCRIPTION "Temperature is inside the high warning limit." --#TYPE "Temperature 1 below high warning limit" --#SUMMARY "Temperature %s below %d in %s at %s" --#ARGUMENTS {2,3,0,1} --#SEVERITY INFORMATIONAL --#TIMEINDEX 4 --#STATE NONOPERATIONAL ::= 107 rms-cTemp1HighControlLimitNormal TRAP-TYPE ENTERPRISE rms-cTemp1 VARIABLES { sysDescr, sysName, rms-cTemp1Name, rms-cTemp1UpperControlLevel } DESCRIPTION "Temperature is inside the high control limit." --#TYPE "Temperature 1 below high control limit" --#SUMMARY "Temperature %s below %d in %s at %s" --#ARGUMENTS {2,3,0,1} --#SEVERITY INFORMATIONAL --#TIMEINDEX 4 --#STATE NONOPERATIONAL ::= 108 -- }}} -- {{{ rms-cHumid rms-cHumid1EnableMonitoring OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting to one enables monitoring of Humidity" ::= { rms-cHumid1 1 } rms-cHumid1Name OBJECT-TYPE SYNTAX DisplayString (SIZE(0..47)) ACCESS read-write STATUS mandatory DESCRIPTION "The name of the humidity reading" ::= { rms-cHumid1 2 } rms-cHumid1CalibrationOffset OBJECT-TYPE SYNTAX INTEGER (-100..100) ACCESS read-write STATUS mandatory DESCRIPTION "Calibration offset in 0.1 percent" ::= { rms-cHumid1 3 } rms-cHumid1Current OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-only STATUS mandatory DESCRIPTION "The current humidity reading in 0.1%" ::= { rms-cHumid1 4 } rms-cHumid1Thresholds OBJECT IDENTIFIER ::= { rms-cHumid1 5 } rms-cHumid1OFFtoONtraps OBJECT IDENTIFIER ::= { rms-cHumid1 6 } rms-cHumid1OFFtoONrepeatTimers OBJECT IDENTIFIER ::= { rms-cHumid1 7 } rms-cHumid1ONtoOFFtraps OBJECT IDENTIFIER ::= { rms-cHumid1 8 } rms-cHumid1ONtoOFFrepeatTimers OBJECT IDENTIFIER ::= { rms-cHumid1 9 } -- {{{ rms-cHumidThresholds rms-cHumid1LowerControlLevel OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-write STATUS mandatory DESCRIPTION "The Lower Limit Humidity threshold in 0.1 percent" ::= { rms-cHumid1Thresholds 1 } rms-cHumid1LowerWarningLevel OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-write STATUS mandatory DESCRIPTION "The Lower Control humidity threshold in 0.1 percent" ::= { rms-cHumid1Thresholds 2 } rms-cHumid1UpperWarningLevel OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-write STATUS mandatory DESCRIPTION "The Upper Control humidity threshold in 0.1 percent" ::= { rms-cHumid1Thresholds 3 } rms-cHumid1UpperControlLevel OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-write STATUS mandatory DESCRIPTION "The Upper Limit humidity threshold in 0.1 percent" ::= { rms-cHumid1Thresholds 4 } -- }}} -- {{{ rms-cTempOFFtoONtraps rms-cHumid1OFFtoONtrapLCL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cHumid1OFFtoONtraps 1 } rms-cHumid1OFFtoONtrapLWL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cHumid1OFFtoONtraps 2 } rms-cHumid1OFFtoONtrapUWL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cHumid1OFFtoONtraps 3 } rms-cHumid1OFFtoONtrapUCL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cHumid1OFFtoONtraps 4 } -- }}} -- {{{ rms-cHumidOFFtoONrepeatTimers rms-cHumid1OFFtoONrepLCL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cHumid1OFFtoONrepeatTimers 1 } rms-cHumid1OFFtoONrepLWL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cHumid1OFFtoONrepeatTimers 2 } rms-cHumid1OFFtoONrepUWL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cHumid1OFFtoONrepeatTimers 3 } rms-cHumid1OFFtoONrepUCL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cHumid1OFFtoONrepeatTimers 4 } -- }}} -- {{{ rms-cTempONtoOFFtraps rms-cHumid1ONtoOFFtrapLCL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cHumid1ONtoOFFtraps 1 } rms-cHumid1ONtoOFFtrapLWL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cHumid1ONtoOFFtraps 2 } rms-cHumid1ONtoOFFtrapUWL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cHumid1ONtoOFFtraps 3 } rms-cHumid1ONtoOFFtrapUCL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cHumid1ONtoOFFtraps 4 } -- }}} -- {{{ rms-cHumidONtoOFFrepeatTimers rms-cHumid1ONtoOFFrepLCL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cHumid1ONtoOFFrepeatTimers 1 } rms-cHumid1ONtoOFFrepLWL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cHumid1ONtoOFFrepeatTimers 2 } rms-cHumid1ONtoOFFrepUWL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cHumid1ONtoOFFrepeatTimers 3 } rms-cHumid1ONtoOFFrepUCL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cHumid1ONtoOFFrepeatTimers 4 } -- }}} -- {{{ rms-cTemp rms-cTemp2EnableMonitoring OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting to one enables monitoring of Temperature" ::= { rms-cTemp2 1 } rms-cTemp2Name OBJECT-TYPE SYNTAX DisplayString (SIZE(0..47)) ACCESS read-write STATUS mandatory DESCRIPTION "The name of the temperature reading" ::= { rms-cTemp2 2 } rms-cTemp2CalibrationOffset OBJECT-TYPE SYNTAX INTEGER (-100..100) ACCESS read-write STATUS mandatory DESCRIPTION "Calibration offset in 0.1 degrees" ::= { rms-cTemp2 3 } rms-cTemp2Current OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-only STATUS mandatory DESCRIPTION "The current temperature reading in 0.1%" ::= { rms-cTemp2 4 } rms-cTemp2Thresholds OBJECT IDENTIFIER ::= { rms-cTemp2 5 } rms-cTemp2OFFtoONtraps OBJECT IDENTIFIER ::= { rms-cTemp2 6 } rms-cTemp2OFFtoONrepeatTimers OBJECT IDENTIFIER ::= { rms-cTemp2 7 } rms-cTemp2ONtoOFFtraps OBJECT IDENTIFIER ::= { rms-cTemp2 8 } rms-cTemp2ONtoOFFrepeatTimers OBJECT IDENTIFIER ::= { rms-cTemp2 9 } -- {{{ rms-cTempThresholds rms-cTemp2LowerControlLevel OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-write STATUS mandatory DESCRIPTION "The Lower Limit temperature threshold in 0.1 degrees" ::= { rms-cTemp2Thresholds 1 } rms-cTemp2LowerWarningLevel OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-write STATUS mandatory DESCRIPTION "The Lower Control temperature threshold in 0.1 degrees" ::= { rms-cTemp2Thresholds 2 } rms-cTemp2UpperWarningLevel OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-write STATUS mandatory DESCRIPTION "The Upper Control temperature threshold in 0.1 degrees" ::= { rms-cTemp2Thresholds 3 } rms-cTemp2UpperControlLevel OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-write STATUS mandatory DESCRIPTION "The Upper Limit temperature threshold in 0.1 degrees" ::= { rms-cTemp2Thresholds 4 } -- }}} -- {{{ rms-cTempOFFtoONtraps rms-cTemp2OFFtoONtrapLCL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cTemp2OFFtoONtraps 1 } rms-cTemp2OFFtoONontrapLWL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cTemp2OFFtoONtraps 2 } rms-cTemp2OFFtoONtrapUWL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cTemp2OFFtoONtraps 3 } rms-cTemp2OFFtoONtrapUCL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cTemp2OFFtoONtraps 4 } -- }}} -- {{{ rms-cTempOFFtoONrepeatTimers rms-cTemp2OFFtoONrepLCL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cTemp2OFFtoONrepeatTimers 1 } rms-cTemp2OFFtoONrepLWL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cTemp2OFFtoONrepeatTimers 2 } rms-cTemp2OFFtoONrepUWL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cTemp2OFFtoONrepeatTimers 3 } rms-cTemp2OFFtoONrepUCL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cTemp2OFFtoONrepeatTimers 4 } -- }}} -- {{{ rms-cTempONtoOFFtraps rms-cTemp2ONtoOFFtrapLCL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cTemp2ONtoOFFtraps 1 } rms-cTemp2ONtoOFFtrapLWL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cTemp2ONtoOFFtraps 2 } rms-cTemp2ONtoOFFtrapUWL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cTemp2ONtoOFFtraps 3 } rms-cTemp2ONtoOFFtrapUCL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cTemp2ONtoOFFtraps 4 } -- }}} -- {{{ rms-cTempONtoOFFrepeatTimers rms-cTemp2ONtoOFFrepLCL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cTemp2ONtoOFFrepeatTimers 1 } rms-cTemp2ONtoOFFrepLWL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cTemp2ONtoOFFrepeatTimers 2 } rms-cTemp2ONtoOFFrepUWL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cTemp2ONtoOFFrepeatTimers 3 } rms-cTemp2ONtoOFFrepUCL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cTemp2ONtoOFFrepeatTimers 4 } -- }}} -- {{{ rms-cHumid rms-cHumid2EnableMonitoring OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Setting to one enables monitoring of Humidity" ::= { rms-cHumid2 1 } rms-cHumid2Name OBJECT-TYPE SYNTAX DisplayString (SIZE(0..47)) ACCESS read-write STATUS mandatory DESCRIPTION "The name of the humidity reading" ::= { rms-cHumid2 2 } rms-cHumid2CalibrationOffset OBJECT-TYPE SYNTAX INTEGER (-100..100) ACCESS read-write STATUS mandatory DESCRIPTION "Calibration offset in 0.1 percent" ::= { rms-cHumid2 3 } rms-cHumid2Current OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-only STATUS mandatory DESCRIPTION "The current humidity reading in 0.1%" ::= { rms-cHumid2 4 } rms-cHumid2Thresholds OBJECT IDENTIFIER ::= { rms-cHumid2 5 } rms-cHumid2OFFtoONtraps OBJECT IDENTIFIER ::= { rms-cHumid2 6 } rms-cHumid2OFFtoONrepeatTimers OBJECT IDENTIFIER ::= { rms-cHumid2 7 } rms-cHumid2ONtoOFFtraps OBJECT IDENTIFIER ::= { rms-cHumid2 8 } rms-cHumid2ONtoOFFrepeatTimers OBJECT IDENTIFIER ::= { rms-cHumid2 9 } -- {{{ rms-cHumidThresholds rms-cHumid2LowerControlLevel OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-write STATUS mandatory DESCRIPTION "The Lower Limit Humidity threshold in 0.1 percent" ::= { rms-cHumid2Thresholds 1 } rms-cHumid2LowerWarningLevel OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-write STATUS mandatory DESCRIPTION "The Lower Control humidity threshold in 0.1 percent" ::= { rms-cHumid2Thresholds 2 } rms-cHumid2UpperWarningLevel OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-write STATUS mandatory DESCRIPTION "The Upper Control humidity threshold in 0.1 percent" ::= { rms-cHumid2Thresholds 3 } rms-cHumid2UpperControlLevel OBJECT-TYPE SYNTAX INTEGER (-200..1000) ACCESS read-write STATUS mandatory DESCRIPTION "The Upper Limit humidity threshold in 0.1 percent" ::= { rms-cHumid2Thresholds 4 } -- }}} -- {{{ rms-cTempOFFtoONtraps rms-cHumid2OFFtoONtrapLCL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cHumid2OFFtoONtraps 1 } rms-cHumid2OFFtoONtrapLWL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cHumid2OFFtoONtraps 2 } rms-cHumid2OFFtoONtrapUWL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cHumid2OFFtoONtraps 3 } rms-cHumid2OFFtoONtrapUCL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cHumid2OFFtoONtraps 4 } -- }}} -- {{{ rms-cHumidOFFtoONrepeatTimers rms-cHumid2OFFtoONrepLCL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cHumid2OFFtoONrepeatTimers 1 } rms-cHumid2OFFtoONrepLWL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cHumid2OFFtoONrepeatTimers 2 } rms-cHumid2OFFtoONrepUWL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cHumid2OFFtoONrepeatTimers 3 } rms-cHumid2OFFtoONrepUCL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cHumid2OFFtoONrepeatTimers 4 } -- }}} -- {{{ rms-cTempONtoOFFtraps rms-cHumid2ONtoOFFtrapLCL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cHumid2ONtoOFFtraps 1 } rms-cHumid2ONtoOFFtrapLWL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cHumid2ONtoOFFtraps 2 } rms-cHumid2ONtoOFFtrapUWL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cHumid2ONtoOFFtraps 3 } rms-cHumid2ONtoOFFtrapUCL OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cHumid2ONtoOFFtraps 4 } -- }}} -- {{{ rms-cHumidONtoOFFrepeatTimers rms-cHumid2ONtoOFFrepLCL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cHumid2ONtoOFFrepeatTimers 1 } rms-cHumid2ONtoOFFrepLWL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cHumid2ONtoOFFrepeatTimers 2 } rms-cHumid2ONtoOFFrepUWL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cHumid2ONtoOFFrepeatTimers 3 } rms-cHumid2ONtoOFFrepUCL OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cHumid2ONtoOFFrepeatTimers 4 } -- }}} -- {{{ rms-cContact group rms-cContactNames OBJECT IDENTIFIER ::= { rms-cContact 1 } rms-cContactType OBJECT IDENTIFIER ::= { rms-cContact 2 } rms-cContactReset OBJECT IDENTIFIER ::= { rms-cContact 3 } rms-cContactNormalStates OBJECT IDENTIFIER ::= { rms-cContact 4 } rms-cContactCurrentStates OBJECT IDENTIFIER ::= { rms-cContact 5 } rms-cContactOFFtoONtraps OBJECT IDENTIFIER ::= { rms-cContact 6 } rms-cContactOFFtoONrepeatTimers OBJECT IDENTIFIER ::= { rms-cContact 7 } rms-cContactONtoOFFtraps OBJECT IDENTIFIER ::= { rms-cContact 8 } rms-cContactONtoOFFrepeatTimers OBJECT IDENTIFIER ::= { rms-cContact 9 } -- {{{ rms-cContactNames group rms-cContact1Name OBJECT-TYPE SYNTAX DisplayString (SIZE(0..47)) ACCESS read-write STATUS mandatory DESCRIPTION "The name of the contact" ::= { rms-cContactNames 1 } rms-cContact2Name OBJECT-TYPE SYNTAX DisplayString (SIZE(0..47)) ACCESS read-write STATUS mandatory DESCRIPTION "The name of the contact" ::= { rms-cContactNames 2 } rms-cContact3Name OBJECT-TYPE SYNTAX DisplayString (SIZE(0..47)) ACCESS read-write STATUS mandatory DESCRIPTION "The name of the contact" ::= { rms-cContactNames 3 } rms-cContact4Name OBJECT-TYPE SYNTAX DisplayString (SIZE(0..47)) ACCESS read-write STATUS mandatory DESCRIPTION "The name of the contact" ::= { rms-cContactNames 4 } rms-cContact5Name OBJECT-TYPE SYNTAX DisplayString (SIZE(0..47)) ACCESS read-write STATUS mandatory DESCRIPTION "The name of the contact" ::= { rms-cContactNames 5 } rms-cContact6Name OBJECT-TYPE SYNTAX DisplayString (SIZE(0..47)) ACCESS read-write STATUS mandatory DESCRIPTION "The name of the contact" ::= { rms-cContactNames 6 } rms-cContact7Name OBJECT-TYPE SYNTAX DisplayString (SIZE(0..47)) ACCESS read-write STATUS mandatory DESCRIPTION "The name of the contact" ::= { rms-cContactNames 7 } rms-cContact8Name OBJECT-TYPE SYNTAX DisplayString (SIZE(0..47)) ACCESS read-write STATUS mandatory DESCRIPTION "The name of the contact" ::= { rms-cContactNames 8 } -- }}} -- {{{ rms-cContactType group rms-cContact1Type OBJECT-TYPE SYNTAX INTEGER { level(0), positive-edge(1), negative-edge(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Level or posedge or negedge input detection " ::= { rms-cContactType 1 } rms-cContact2Type OBJECT-TYPE SYNTAX INTEGER { level(0), positive-edge(1), negative-edge(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Level or posedge or negedge input detection " ::= { rms-cContactType 2 } rms-cContact3Type OBJECT-TYPE SYNTAX INTEGER { level(0), positive-edge(1), negative-edge(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Level or posedge or negedge input detection " ::= { rms-cContactType 3 } rms-cContact4Type OBJECT-TYPE SYNTAX INTEGER { level(0), positive-edge(1), negative-edge(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Level or posedge or negedge input detection " ::= { rms-cContactType 4 } rms-cContact5Type OBJECT-TYPE SYNTAX INTEGER { level(0), positive-edge(1), negative-edge(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Level or posedge or negedge input detection " ::= { rms-cContactType 5 } rms-cContact6Type OBJECT-TYPE SYNTAX INTEGER { level(0), positive-edge(1), negative-edge(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Level or posedge or negedge input detection " ::= { rms-cContactType 6 } rms-cContact7Type OBJECT-TYPE SYNTAX INTEGER { level(0), positive-edge(1), negative-edge(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Level or posedge or negedge input detection " ::= { rms-cContactType 7 } rms-cContact8Type OBJECT-TYPE SYNTAX INTEGER { level(0), positive-edge(1), negative-edge(2) } ACCESS read-write STATUS mandatory DESCRIPTION "Level or posedge or negedge input detection " ::= { rms-cContactType 8 } -- }}} -- {{{ rms-cContactReset group rms-cContact1Reset OBJECT-TYPE SYNTAX INTEGER { reset(1) } ACCESS write-only STATUS mandatory DESCRIPTION "Resets edge triggered input" ::= { rms-cContactReset 1 } rms-cContact2Reset OBJECT-TYPE SYNTAX INTEGER { reset(1) } ACCESS write-only STATUS mandatory DESCRIPTION "Resets edge triggered input" ::= { rms-cContactReset 2 } rms-cContact3Reset OBJECT-TYPE SYNTAX INTEGER { reset(1) } ACCESS write-only STATUS mandatory DESCRIPTION "Resets edge triggered input " ::= { rms-cContactReset 3 } rms-cContact4Reset OBJECT-TYPE SYNTAX INTEGER { reset(1) } ACCESS write-only STATUS mandatory DESCRIPTION "Resets edge triggered input " ::= { rms-cContactReset 4 } rms-cContact5Reset OBJECT-TYPE SYNTAX INTEGER { reset(1) } ACCESS write-only STATUS mandatory DESCRIPTION "Resets edge triggered input" ::= { rms-cContactReset 5 } rms-cContact6Reset OBJECT-TYPE SYNTAX INTEGER { reset(1) } ACCESS write-only STATUS mandatory DESCRIPTION "Resets edge triggered input " ::= { rms-cContactReset 6 } rms-cContact7Reset OBJECT-TYPE SYNTAX INTEGER { reset(1) } ACCESS write-only STATUS mandatory DESCRIPTION "Resets edge triggered input " ::= { rms-cContactReset 7 } rms-cContact8Reset OBJECT-TYPE SYNTAX INTEGER { reset(1) } ACCESS write-only STATUS mandatory DESCRIPTION "Resets edge triggered input " ::= { rms-cContactReset 8 } -- }}} -- {{{ rms-cContactNormalStates group rms-cContact1NormalState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for normally open condition, 1 for normally closed" ::= { rms-cContactNormalStates 1 } rms-cContact2NormalState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for normally open condition, 1 for normally closed" ::= { rms-cContactNormalStates 2 } rms-cContact3NormalState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for normally open condition, 1 for normally closed" ::= { rms-cContactNormalStates 3 } rms-cContact4NormalState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for normally open condition, 1 for normally closed" ::= { rms-cContactNormalStates 4 } rms-cContact5NormalState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for normally open condition, 1 for normally closed" ::= { rms-cContactNormalStates 5 } rms-cContact6NormalState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for normally open condition, 1 for normally closed" ::= { rms-cContactNormalStates 6 } rms-cContact7NormalState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for normally open condition, 1 for normally closed" ::= { rms-cContactNormalStates 7 } rms-cContact8NormalState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for normally open condition, 1 for normally closed" ::= { rms-cContactNormalStates 8 } -- }}} -- {{{ rms-cContactCurrentStates group rms-cContact1CurrentState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-only STATUS mandatory DESCRIPTION "The current state of the contact" ::= { rms-cContactCurrentStates 1 } rms-cContact2CurrentState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-only STATUS mandatory DESCRIPTION "The current state of the contact" ::= { rms-cContactCurrentStates 2 } rms-cContact3CurrentState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-only STATUS mandatory DESCRIPTION "The current state of the contact" ::= { rms-cContactCurrentStates 3 } rms-cContact4CurrentState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-only STATUS mandatory DESCRIPTION "The current state of the contact" ::= { rms-cContactCurrentStates 4 } rms-cContact5CurrentState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-only STATUS mandatory DESCRIPTION "The current state of the contact" ::= { rms-cContactCurrentStates 5 } rms-cContact6CurrentState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-only STATUS mandatory DESCRIPTION "The current state of the contact" ::= { rms-cContactCurrentStates 6 } rms-cContact7CurrentState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-only STATUS mandatory DESCRIPTION "The current state of the contact" ::= { rms-cContactCurrentStates 7 } rms-cContact8CurrentState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-only STATUS mandatory DESCRIPTION "The current state of the contact" ::= { rms-cContactCurrentStates 8 } -- }}} -- {{{ rms-cContactOFFtoONtraps rms-cContact1OFFtoONtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cContactOFFtoONtraps 1 } rms-cContact2OFFtoONtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cContactOFFtoONtraps 2 } rms-cContact3OFFtoONtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cContactOFFtoONtraps 3 } rms-cContact4OFFtoONtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cContactOFFtoONtraps 4 } rms-cContact5OFFtoONtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cContactOFFtoONtraps 5 } rms-cContact6OFFtoONtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cContactOFFtoONtraps 6 } rms-cContact7OFFtoONtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cContactOFFtoONtraps 7 } rms-cContact8OFFtoONtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cContactOFFtoONtraps 8 } -- }}} -- {{{ rms-cContactOFFtoONrepeatTimers rms-cContact1OFFtoONrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cContactOFFtoONrepeatTimers 1 } rms-cContact2OFFtoONrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cContactOFFtoONrepeatTimers 2 } rms-cContact3OFFtoONrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cContactOFFtoONrepeatTimers 3 } rms-cContact4OFFtoONrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cContactOFFtoONrepeatTimers 4 } rms-cContact5OFFtoONrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cContactOFFtoONrepeatTimers 5 } rms-cContact6OFFtoONrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cContactOFFtoONrepeatTimers 6 } rms-cContact7OFFtoONrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cContactOFFtoONrepeatTimers 7 } rms-cContact8OFFtoONrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cContactOFFtoONrepeatTimers 8 } -- }}} -- {{{ rms-cContactONtoOFFtraps rms-cContact1ONtoOFFtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cContactONtoOFFtraps 1 } rms-cContact2ONtoOFFtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cContactONtoOFFtraps 2 } rms-cContact3ONtoOFFtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cContactONtoOFFtraps 3 } rms-cContact4ONtoOFFtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cContactONtoOFFtraps 4 } rms-cContact5ONtoOFFtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cContactONtoOFFtraps 5 } rms-cContact6ONtoOFFtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cContactONtoOFFtraps 6 } rms-cContact7ONtoOFFtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cContactONtoOFFtraps 7 } rms-cContact8ONtoOFFtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cContactONtoOFFtraps 8 } -- }}} -- {{{ rms-cContactONtoOFFrepeatTimers rms-cContact1ONtoOFFrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cContactONtoOFFrepeatTimers 1 } rms-cContact2ONtoOFFrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cContactONtoOFFrepeatTimers 2 } rms-cContact3ONtoOFFrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cContactONtoOFFrepeatTimers 3 } rms-cContact4ONtoOFFrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cContactONtoOFFrepeatTimers 4 } rms-cContact5ONtoOFFrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cContactONtoOFFrepeatTimers 5 } rms-cContact6ONtoOFFrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cContactONtoOFFrepeatTimers 6 } rms-cContact7ONtoOFFrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cContactONtoOFFrepeatTimers 7 } rms-cContact8ONtoOFFrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cContactONtoOFFrepeatTimers 8 } -- }}} -- {{{ rms-cOutput group rms-cOutputEnables OBJECT IDENTIFIER ::= { rms-cOutput 1 } rms-cOutputNames OBJECT IDENTIFIER ::= { rms-cOutput 2 } rms-cOutputStates OBJECT IDENTIFIER ::= { rms-cOutput 3 } rms-cOutputBooleanStates OBJECT IDENTIFIER ::= { rms-cOutput 4 } rms-cOutputOnDelay OBJECT IDENTIFIER ::= { rms-cOutput 5 } rms-cOutputOffDelay OBJECT IDENTIFIER ::= { rms-cOutput 6 } rms-cOutputStrings OBJECT IDENTIFIER ::= { rms-cOutput 7 } rms-cOutputBooleanSelector OBJECT IDENTIFIER ::= { rms-cOutput 8 } rms-cOutputOFFtoONtraps OBJECT IDENTIFIER ::= { rms-cOutput 9 } rms-cOutputOFFtoONrepeatTimers OBJECT IDENTIFIER ::= { rms-cOutput 10 } rms-cOutputONtoOFFtraps OBJECT IDENTIFIER ::= { rms-cOutput 11 } rms-cOutputONtoOFFrepeatTimers OBJECT IDENTIFIER ::= { rms-cOutput 12 } -- {{{ rms-cOutputEnables group rms-cOutput1Enable OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to one enables the output" ::= { rms-cOutputEnables 1 } rms-cOutput2Enable OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to one enables the output" ::= { rms-cOutputEnables 2 } rms-cOutput3Enable OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to one enables the output" ::= { rms-cOutputEnables 3 } --rms-cOutput4Enable OBJECT-TYPE -- SYNTAX INTEGER { off(0), on(1) } -- ACCESS read-write -- STATUS mandatory -- DESCRIPTION -- "Set to one enables the output" -- ::= { rms-cOutputEnables 4 } -- }}} -- {{{ rms-cOutputNames group rms-cOutput1Name OBJECT-TYPE SYNTAX DisplayString (SIZE(0..47)) ACCESS read-write STATUS mandatory DESCRIPTION "The name of the output" ::= { rms-cOutputNames 1 } rms-cOutput2Name OBJECT-TYPE SYNTAX DisplayString (SIZE(0..47)) ACCESS read-write STATUS mandatory DESCRIPTION "The name of the output" ::= { rms-cOutputNames 2 } rms-cOutput3Name OBJECT-TYPE SYNTAX DisplayString (SIZE(0..47)) ACCESS read-write STATUS mandatory DESCRIPTION "The name of the output" ::= { rms-cOutputNames 3 } rms-cOutput4Name OBJECT-TYPE SYNTAX DisplayString (SIZE(0..47)) ACCESS read-write STATUS mandatory DESCRIPTION "The name of the output" ::= { rms-cOutputNames 4 } -- }}} -- {{{ rms-cOutputNormalStates group rms-cOutput1State OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Default State for the output" ::= { rms-cOutputStates 1 } rms-cOutput2State OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Default State for the output" ::= { rms-cOutputStates 2 } rms-cOutput3State OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Default State for the output" ::= { rms-cOutputStates 3 } --rms-cOutput4State OBJECT-TYPE -- SYNTAX INTEGER { off(0), on(1) } -- ACCESS read-write -- STATUS mandatory -- DESCRIPTION -- "Default State for the output" -- ::= { rms-cOutputStates 4 } -- }}} -- {{{ rms-cOutputCurrentStates group rms-cOutput1BooleanState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-only STATUS mandatory DESCRIPTION "Set as a result of the AND/OR comparison" ::= { rms-cOutputBooleanStates 1 } rms-cOutput2BooleanState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-only STATUS mandatory DESCRIPTION "Set as a result of the AND/OR comparison" ::= { rms-cOutputBooleanStates 2 } rms-cOutput3BooleanState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-only STATUS mandatory DESCRIPTION "Set as a result of the AND/OR comparison" ::= { rms-cOutputBooleanStates 3 } rms-cOutput4BooleanState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } ACCESS read-only STATUS mandatory DESCRIPTION "Set as a result of the AND/OR comparison" ::= { rms-cOutputBooleanStates 4 } -- }}} -- {{{ rms-cOutputOnDelay group rms-cOutput1OnDelay OBJECT-TYPE SYNTAX INTEGER (0..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Delay in seconds for the activation of the output in response to a change into the on state" ::= { rms-cOutputOnDelay 1 } rms-cOutput2OnDelay OBJECT-TYPE SYNTAX INTEGER (0..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Delay in seconds for the activation of the output in response to a change into the on state" ::= { rms-cOutputOnDelay 2 } rms-cOutput3OnDelay OBJECT-TYPE SYNTAX INTEGER (0..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Delay in seconds for the activation of the output in response to a change into the on state" ::= { rms-cOutputOnDelay 3 } rms-cOutput4OnDelay OBJECT-TYPE SYNTAX INTEGER (0..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Delay in seconds for the activation of the output in response to a change into the on state" ::= { rms-cOutputOnDelay 4 } -- }}} -- {{{ rms-cOutputOffDelay group rms-cOutput1OffDelay OBJECT-TYPE SYNTAX INTEGER (0..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Delay in seconds for the activation of the output in response to a change into the OFF state" ::= { rms-cOutputOffDelay 1 } rms-cOutput2OffDelay OBJECT-TYPE SYNTAX INTEGER (0..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Delay in seconds for the activation of the output in response to a change into the OFF state" ::= { rms-cOutputOffDelay 2 } rms-cOutput3OffDelay OBJECT-TYPE SYNTAX INTEGER (0..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Delay in seconds for the activation of the output in response to a change into the OFF state" ::= { rms-cOutputOffDelay 3 } rms-cOutput4OffDelay OBJECT-TYPE SYNTAX INTEGER (0..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Delay in seconds for the activation of the output in response to a change into the OFF state" ::= { rms-cOutputOffDelay 4 } -- }}} -- {{{ rms-cOutputAndStrings group rms-cOutput1BooleanInput OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Tn=temperature source, n is one of the following subindex:1->Temp1 LCL,2->Temp1 LWL, 3->Temp1 UWL,4->Temp1 UCL,5->Temp2 LCL,6->Temp2 LWL,7->Temp2 UWL,8->Temp2 UCL. Cn=contact source, n is the contact order number. No spaces used. Max 12 inputs" ::= { rms-cOutputStrings 1 } rms-cOutput2BooleanInput OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Tn=temperature source, n is one of the following subindex:1->Temp1 LCL,2->Temp1 LWL, 3->Temp1 UWL,4->Temp1 UCL,5->Temp2 LCL,6->Temp2 LWL,7->Temp2 UWL,8->Temp2 UCL. Cn=contact source, n is the contact order number. No spaces used. Max 12 inputs" ::= { rms-cOutputStrings 2 } rms-cOutput3BooleanInput OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Tn=temperature source, n is one of the following subindex:1->Temp1 LCL,2->Temp1 LWL, 3->Temp1 UWL,4->Temp1 UCL,5->Temp2 LCL,6->Temp2 LWL,7->Temp2 UWL,8->Temp2 UCL. Cn=contact source, n is the contact order number. No spaces used. Max 12 inputs" ::= { rms-cOutputStrings 3 } rms-cOutput4BooleanInput OBJECT-TYPE SYNTAX DisplayString ACCESS read-write STATUS mandatory DESCRIPTION "Tn=temperature source, n is one of the following subindex:1->Temp1 LCL,2->Temp1 LWL, 3->Temp1 UWL,4->Temp1 UCL,5->Temp2 LCL,6->Temp2 LWL,7->Temp2 UWL,8->Temp2 UCL. Cn=contact source, n is the contact order number. No spaces used. Max 12 inputs" ::= { rms-cOutputStrings 4 } -- }}} -- {{{ rms-cOutputBooleanSelector group rms-cOutput1BooleanSelector OBJECT-TYPE SYNTAX INTEGER { or(0), and(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set 0 to select OR, and 1 to select AND" ::= { rms-cOutputBooleanSelector 1 } rms-cOutput2BooleanSelector OBJECT-TYPE SYNTAX INTEGER { or(0), and(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set 0 to select OR, and 1 to select AND" ::= { rms-cOutputBooleanSelector 2 } rms-cOutput3BooleanSelector OBJECT-TYPE SYNTAX INTEGER { or(0), and(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set 0 to select OR, and 1 to select AND" ::= { rms-cOutputBooleanSelector 3 } rms-cOutput4BooleanSelector OBJECT-TYPE SYNTAX INTEGER { or(0), and(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set 0 to select OR, and 1 to select AND" ::= { rms-cOutputBooleanSelector 4 } -- }}} -- {{{ rms-cOutputOFFtoONtraps group rms-cOutput1OFFtoONtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cOutputOFFtoONtraps 1 } rms-cOutput2OFFtoONtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cOutputOFFtoONtraps 2 } rms-cOutput3OFFtoONtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cOutputOFFtoONtraps 3 } rms-cOutput4OFFtoONtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cOutputOFFtoONtraps 4 } -- }}} -- {{{ rms-cOutputOFFtoONrepeatTimers group rms-cOutput1OFFtoONrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cOutputOFFtoONrepeatTimers 1 } rms-cOutput2OFFtoONrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cOutputOFFtoONrepeatTimers 2 } rms-cOutput3OFFtoONrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cOutputOFFtoONrepeatTimers 3 } rms-cOutput4OFFtoONrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cOutputOFFtoONrepeatTimers 4 } -- }}} -- {{{ rms-cOutputONtoOFFtraps group rms-cOutput1ONtoOFFtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cOutputONtoOFFtraps 1 } rms-cOutput2ONtoOFFtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cOutputONtoOFFtraps 2 } rms-cOutput3ONtoOFFtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cOutputONtoOFFtraps 3 } rms-cOutput4ONtoOFFtrap OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for trap disabled, 1 for enabled" ::= { rms-cOutputONtoOFFtraps 4 } -- }}} -- {{{ rms-cOutputONtoOFFrepeatTimers group rms-cOutput1ONtoOFFrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cOutputONtoOFFrepeatTimers 1 } rms-cOutput2ONtoOFFrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cOutputONtoOFFrepeatTimers 2 } rms-cOutput3ONtoOFFrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cOutputONtoOFFrepeatTimers 3 } rms-cOutput4ONtoOFFrep OBJECT-TYPE SYNTAX INTEGER (30..32000) ACCESS read-write STATUS mandatory DESCRIPTION "Set to 0 for no repetion after the first trap is sent, any other integer for the interval in seconds" ::= { rms-cOutputONtoOFFrepeatTimers 4 } -- }}} END